5. Setting up the device
23
Menu group level
5.4.5. Analog output parameters 1
Menu level
Menu level
Parameterisation level
Selection reference of analog output,
OutPt:
Default:
actua
The analog output signal can refer to different functions, in detail these are the current
measurand, the min-value, the max-value, the totaliser/sum function, the constant value or the
difference between current measurand and constant value. If
HoLd
was selected, the signal of
the analog output will be kept. It can be continued processing after a deactivation of
Hold
. With
[P]
the selection is confirmed and the device changes into menu level.
Selection analog output,
Out.rA:
Default:
4-20
Three output signals are available 0-10 VDC, 0-20 mA and 4-20 mA. Select the desired signal
with this function.
Setting the upper value of the analog output,
Out.En:
Default:
10000
The final value is adjusted from the smallest to the highest digit with
[
▲
] [
▼
]
and confirmed
digit per digit with
[P]
. A minus sign can only be parameterised on the leftmost digit. After the
last digit the device changes back into menu level.
Setting the lower value of the analog output,
Out.OF:
Default:
00000
The initial value is adjusted from the smallest to the highest digit with
[
▲
] [
▼
]
and confirmed
digit per digit with
[P]
. A minus sign can only be parameterised on the leftmost digit. After the
last digit the device changes back into menu level.