5. Setting up the device
21
Menu level
Parameterisation level
User code,
U.Code:
Default:
000o
Via this code reduced sets of parameters can released. A change of the
U.CodE
can be done via
the correct input of the
A.CodE
(master code).
Master code,
A.Code:
Default:
1234
By entering
A.CodE
the device will be unlocked and all parameters are released.
Release/lock analog output parameters,
Out.LE:
Default:
all
Analog output parameter can be locked or released for the user:
-
En-oF:
the initial or final value can be changed in operation mode
-
Out.EO:
the output signal can be changed from e.g. 0-20 mA to 4-20 mA or 0-10 VDC
-
ALL:
analog output parameters are released
-
no:
all analog output parameters are locked
Release/lock alarm parameters,
AL.LEU:
Default:
all
This parameter describes the user release/user lock of the alarm:
- LIMIt
: here only the range of value of the threshold values 1-4 can be changed
-
ALrM.L
: here the range of value and the alarm trigger can be changed
-
ALL:
all alarm parameters are released
-
no:
all alarm parameters are locked
Back to menu group level,
rEt
:
With
[P]
the selection is confirmed and the device changes into menu group level
„–Cod–“
.
Menu group level
5.4.3. Safety parameters
Menu level