9
5. Setting up the device
Menu level
Parameterisation level
Setting the upper range value,
END
:
Default:
10000
Set the final value from the smallest to the highest digit with
[
▲
] [
▼
]
and confirm each digit
with
[P]
. A minus sign can only be parameterized on the leftmost digit. After the last digit, the
display switches back to the menu level. If
Sens
was selected as input option, one can only
select between
noca
and
cal.
With
noca
, only the previously set display value is taken over, and
with
cal
, the device takes over both the display value and the analogue input value.
Setting the lower range value,
offs
:
Default:
0
Enter the start/offset value from the smallest to the highest digit
[
▲
] [
▼
]
and confirm each digit
with
[P]
. After the last digit the display switches back to the menu level. If
Sens.F
was selected
as the input option, one can only select between
noca
and
cal.
With
noca
, only the previously set
display value is taken over, and with
cal
, the device takes over both the display value and the
analogue input value.
Setting the comma/decimal point,
dot
:
Default:
0
The decimal point on the display can be moved with
[
▲
] [
▼
]
and confirmed with
[P]
. The
display then switches back to the menu level again.
Setting up the display time,
SEC
:
Default:
1.0
The display time is set with
[
▲
] [
▼
]
. The display moves up in increments of 0.1 up to 1 second
and in increments of 1.0 up to 10.0 second. Confirm the selection by pressing the
[P]
button.
The display then switches back to the menu level again.
Rescale the input frequency,
EndA:
Default:
10000
With this function, one can rescale the input value of
e.g. 8.000 Hz
(works setting) without
applying a measuring signal. If sensor calibration has been selected, these parameters are not
available.
then