3.1 How to configure and test the CAN converters
Configuration Interface:
Step 1. Before power-on the CAN converters, users must set them to the Init mode. Users
need to switch the Init/Normal DIP-Switch to Init position described in the section 2.5.1.
Afterwards, power on the CAN converter and the Run LED indicator will be flashed once per
second.
Step 2. Connect the available COM port of the PC to the CAN converters, and execute the
VxCAN Utility.
Step 3. Click the button
to search all CAN devices connected to the PC.
Step 4. After finishing the search, the CAN converters (for example tM-7530 and I-7530)
which are connecting to the PC or have connected to the PC will be list in the left side of the
VxCAN Utility. If the tM-7530/tM-7530A/tM-7565 is in Init mode, the VxCAN utility shows the
“Init” information in the list.
Step 5. Click the tM-7530-Init in the list, the module configuration dialog is popped up.
Different CAN converters may have the different information in the pop-up dialog. All of the
settings in the module configuration dialog will be saved into the EEPROM of the module.
I-7530, I-7530-FT, I-7530A, I-7565, tM-7530, tM-7530A, tM-7565 User Manual Version 1.5
Page
:
28