the UART message is none, the UART timeout is useful. After receiving one character
from the UART interface, the CAN converter will not transfer the data until the time of the
UART timeout passes.
About details of the pair connection, please refer to the Appendix E for reference.
Save and default value button:
After finishing the configuration, users can click the button “Save All Setting” to save the
configuration in to the EEPROM of the CAN converter. If users would like to recover the
parameters to the factory default, click “Load Default Setting” button to recover all of the
configuration parameters to be default value. Afterwards, users can use the button “Save All
Settings” to save the default parameters in to the EEPROM of the CAN converter.
The default values of the parameters of the CAN converter are shown below.
RS-232:
RS-232 Baud rate = 115200/921600(for I-7565)
Data Bit
= 8
Stop Bit
= 1
Parity
=
None
Add Checksum
= No
Error Response
= No
TimeStamp Response = No
CAN:
CAN
Specification
=
2.0A
CAN bus Baud rate = 125K
Acceptance Code
= 000
Acceptance Mask
= 000
Communication:
Mode: Normal
I-7530, I-7530-FT, I-7530A, I-7565, tM-7530, tM-7530A, tM-7565 User Manual Version 1.5