GroupName
The GroupName for a channel must contain the exact text (case-sensitive) you enter for the
polling definition that the channel included in the config.csv file.
Data Type
32-bit integer and floating-point data uses two registers, as well we 16-bit integer data uses one
register. When setting the ModbusAddr, the corresponding address interval must be reserved
according to the number of registers used by the data type of the specified channel.
Setting
Number
Data Type
Register
Count
Available Range
0
Boolean
1
0,1
1
16-bit Signed Integer
1
-32,768 to 32,767
2
16-bit Unsigned Integer
1
0 to 65,535
3
16-bit Integer in Hex
1
0000 to FFFF
4
32-bit Signed Integer
2
−2,147,483,648 to 2,147,483,647
20
32-bit Signed Integer, Swapped
2
−2,147,483,648 to 2,147,483,647
5
32-bit Unsigned Integer
2
0 to 4,294,967,295
21
32-bit Unsigned Integer, Swapped
2
0 to 4,294,967,295
7
32-bit Floating
2
-3.402E+38 to +3.402E+38
23
32-bit Floating, Swapped
2
-3.402E+38 to +3.402E+38
config.csv
record.csv