3.
Writing data to MDCL to set the holding register in the CL-213 device with
Modbus TCP command
The data of temperature offset written to mapped address 400000 in MDCL with function code 0x06
will be written to the CL-213 in the lobby to change the temperature offset setting in it.
4.
Writing data to MDCL to force multiple coils in the CL-213 device with
Modbus TCP command
Writing the number 1 to the mapped addresses 000000 to 000004 in MDCL with function code 0x0F is
equal to writing 1 to the CL-213 in the lobby to clear high alarm status of temperature, humidity, CO,
CO2 and PM2.5 concentration.