Copyright © 2021 ICP DAS Co., Ltd. All Rights Reserved.
∗
E-mail: [email protected] - 64 -
Description of parameters for a log channel:
Items
Description
Type
#
Defines the active type for a log channel:
“*”: The asterisk symbol denotes that the data logging function of
the specified channel is enabled.
“~”: The swung dash symbol denotes that the data logging function
of the specified channel is disabled.
“”: A blank field denotes that the log channel is unused.
When this field is left blank, the specified channel is not included in
the limit of 120 channels and will not be saved in the MDCL module;
it can be used store configuration of a temporarily unused channel.
Required
GruopName
(*1)
The GroupName entered here must be in line with the GroupName
used in config.csv for the specified channel. If not, the setting becomes
invalid and the data on this channel will not be recorded.
Required
IndexAddr
The index address in its group starting from 0.
Required
DataType
The MDCL supports a variety of data types as follows. The data type
must be exactly the same as the definition of the channel on the slave
device. 16-bit data and 32-bit data use a different number of registers.
When setting the
IndexAddr
parameter, pay attention to the interval
of each type of data.
No.
Data Type
Register
0
Boolean
1
1
16-bit Signed Integer
1
2
16-bit Unsigned Integer
1
3
16-bit Integer in Hex
1
4
32-bit Signed Integer
2
20
32-bit Signed Integer Swapped
2
5
32-bit Unsigned Integer
2
21
32-bit Unsigned Integer Swapped
2
7
32-bit Floating
2
23
32-bit Floating Swapped
2
Required