2 DCON Protocol
All communication with I-87K modules consists of commands
generated by the host and responses transmitted by the I-87K
modules. Each module has a unique ID number that is used for
addressing purposes and is stored in nonvolatile memory. The ID is
00 by default and can be changed using a user command. All
commands to the modules contain the ID address, meaning that
only the addressed module will respond. The only exception to this
are the commands #** (Section 2.2) and ~** (Section 2.27), which
are sent to all modules, but in both of these cases, the modules do
not reply to the command.
Command Format
Leading
Character
Module
Address
Command
[CHKSUM]
CR
Response Format
Leading
Character
Module
Address
Data
[CHKSUM]
CR
CHKSUM A 2-character checksum which is present when the
checksum setting is enabled. See Sections 1.10 (Data
Format Setting) and 2.1 for details.
CR End of command character, carriage return (0x0D)