I-87211W User Manual
42/93
I-87211W User Manual V2.5, Oct. 2010
There will be no response if the command syntax is incorrect,
there is a communication error, or there is no module with the
specified address.
Related Commands:
will reset to safe mode and the DO output
command will be ignored
Examples:
Command: #010001
Response: >
Sets DO0 of the module with address 01 and the
module returns a valid response.
Command :#010016
Response: ?01
Sets DO0 and DO3 to Off, DO1 and DO2 to On
DO6, DO7 and DO8 to Off and DO5 to On
。
This module only includes one DO channel, so the
command is invalid.
Command: #010001
Response: !
A Host WatchDog Timeout was occurred and so the
DO output command is ignored.
Section 2.6 #AA0A (Data)
Section 2.7 #AA1cDD
Section 2.8 #AAAcDD
Section 2.12 $AA6
Section 2.18 @AA
Section 2.19 @AA(Data)