I-7540D CAN-Ethernet Gateway User’s Manual (Version 1.8, March/2021)
88
4.22
99$PPCLLABC
Description:
Change the CAN bus pair connection configuration into EEPROM.
After setting successfully, all parameters will take effective after system restart.
Syntax: 99$PPCLLABC
99$PPC
Command character
LL
number of parameters, here fix to “03”
A
Enable CAN bus pair connection flag, 0: Disable, 1: Enable
B
Using TCP or UDP connection; 0: TCP, 1: UDP
C
Act as a server or client; 0: server, 1: client
Note:
1. When
A
=0,
B
and
C
take no effective
2. When using UDP connection(
B
=1),
C
take no effective
3. When acting as a TCP client or using UDP method, users need
to set the destination IP address (section 4.23), so that the
7540D can work correctly.
Response:
Valid Command: OK
Invalid command: ERROR
Example:
Command (
ASCII
): 99$PPC03101
Command (
HEX
): 39 39 24 50 50 43 30 33 31 30 31
Response: OK
Change the CAN bus pair connection configuration of the 7540D to
“enable CAN bus pair connection” and act as a TCP client.
Note:
1. This command can only be accepted by 7540D’s port
10000
.
2.
Supported by
the fi