EXITING STARTUP MENU - CALIBRATION & TESTING
To exit from the Startup Menu, press and release the STOP button while STARTUP MENU appears on the LCD. If you have
saved changes to the operator speed, PWM Frequency, Open or Close Rampdown, or reset limits, you will be required
to do a quick system calibration. Screen prompts will provide real-time instruction on calibration requirements. See
Page 20 for more detailed information on Calibration.
Once Calibration is completed or if it was not required, the system will run a quick diagnostic, and the LCD will read
indicate its current position (OPEN, CLOSED or STOPPED). The door is now ready for use. BEFORE OPERATING THE DOOR,
ENSURE THAT THE DOOR LIMITS HAVE BEEN SET.
Testing of the door is now required. Observe whether the door is running smoothly and is stopping at the appropriate
limits. Ensure that the door is set at the required speeds, and test each reversing and activation device to confirm their
functionality.
PATENTED BATTERY BACKUP - POWER OUTAGE OPERATION
The Pulse is factory equipped with a patented battery backup system and it is automatically activated during a power
outage. This battery backup even works if there is board damage occuring due to external forces such as lightning or
impact.
Simply push and hold the OPEN button in order to open the door, and push and hold the CLOSE button in order close
the door – the door will respond accordingly, but note that speeds will be reduced. All safety devices will be disabled
during a battery backup operation and any personnel operating the door should maintain a clear line of sight with
the doorway in order to reduce the risk of possible door impact with personnel or equipment, and to ensure the door
operates safely. To enable battery backup functionality when the power is available, please disconnect the power to
the operator.
In case the batteries are fully drained or missing, the base of the motor is also equipped with a 3/8” ratchet entry. TURN
OFF POWER TO THE OPERATOR (even if the power seems out), secure a crankshaft, socket wrench or power drill with 3/8”
ratchet head (not included) inside the ratchet entry and rotate it in the appropriate direction in order to open or close
the door. Turn on the power once manual operation is no longer required.
NOTE ON BATTERIES
Provided lead-acid batteries are 2 x 12V connected in series to provide 24Vdc. The controller provides a monitored
trickle charger in order to maintain the batteries' life. Should the batteries be fully drained and no longer accept
a charge, please replace them with equivalent batteries, and dispose of the expired units according to local
environmental regulations.
CAR WASH/WATER-RESISTANT APPLICATIONS
iControls recommends an available upgrade for all Car Wash/Water Resistant applicaitons. Standard Pulse Operator
Drives are rated IP54, and could be vulnerable to water ingress. Furthermore, reflective photo-eye sensors have
a tendency to be detrimentally affected by condensation on the reflector, preventing reliable operation in such
conditions. iControls offers a cost-effective Water-resistant upgrade that both seals all ingress points, and includes a
thru-beam sensor in place of a reflective photo-eye. Please contact iControls for details and pricing.