SUPPLY VOLTAGE:
110-130, 1ph Input (Standard 3 prong pre-wired cord provided for
electrician-free installation)
BATTERIES:
2 x 0.82Ah
CONTROL VOLTAGE:
24Vdc, 0.8A Power/Connections supplied for activation and
reversing devices
AUX RELAY:
1 SPDT Programmable Relay (factory default to activate on Open
Limits)
Safety
PHOTO-EYE SENSOR:
Polarized Photo-eye Sensor/Reflector with Bracket provided with
unit as non-impact reversing device protection.
POWER OUTAGE
Battery Backup to open/close the door in case of power-outage.
OPERATION:
3/8” ratchet socket for manual crank open/close as added
redundancy.
Maximum Recommended Counter-Balanced Door Size
Pulse 138:
up to 150 Square Feet
Pulse 150:
up to 200 Square Feet
IMPORTANT
WARNING – These instructions are intended for experienced personnel trained for service and
installation of sectional doors and operators. All safety precautions and local codes must be
followed.
1.
READ AND FOLLOW ALL INSTALLATION INSTRUCTIONS.
2.
Have qualified service personnel make necessary repairs to ensure door is operating
smoothly without any unusual noise. Install operator only on a smoothly operating and well
balanced door.
3.
Remove all pull ropes and remove locks (unless mechanically and/or electrically
interlocked to the power unit) connected to the door before installing the operator.
4.
A commercial/industrial door operator that has exposed moving parts capable of causing
injury to persons or employs a motor deemed indirectly accessible by clause 10.6 by virtue
of its location above the floor shall include:
a. Install the door operator at least 2.44m (8 ft) or more above the floor: or
b. If the operator must be installed less than 2.44m (8ft) above the floor, then exposed
moving parts must be protected by covers or guarding; or
c. Both a. and b.
5.
Do not connect the operator to the supply power until instructed to do so.
6.
Locate the push button station: (a) within sight of the door, and (b) at a minimum height of
1.53m (5 ft) above floors, landings, steps, or any other adjacent walking surface and
(c) away from all moving parts.
7.
Install an Entrapment Warning Placard next to the control station in a prominent location.