10 .
Temperature Sensor
(1-4)
1 . Only on-board sensor determines room temperature .
2 . Only remote sensor determines room temperature .
3 . Average temperature of on-board and remote sensor .
4 . Only on-board sensor will be used until NITE period, and then only remote
sensor is used .
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .
9 .
Maximum Cycles Allowed Per Hour
(- -, 2-6)
- - = as many as needed, 2-6 = maximum cycles/hour
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .
8 .
Room Temperature Offset
(+9°F to -9°F) (+4 .5°C to -4 .5°C)
Adjust to calibrate displayed room temperature to match actual room
temperature .
Note:
When not set to 0,
will display
Press the
up
or
down
button to select .
Press the
right
button to advance to the next screen .