28
9.2
ORDINARY
Carry out burner maintenance (as to the specific instructions) and have the calibration checked by duly
qualified personnel.
Check the tightness of flange bolts and the state of the gaskets;
Analyse the system water and make sure it is treated in such a way that scaling does not occur, as
scales would not only reduce the boiler performance, but also cause potentially fatal damage to the boil-
er in the long run.
Make sure that refractory cladding and fume seal gaskets are intact; if they are not, replace them;
Check the integrity of the flame warning light.
Periodically clean the furnace (1) and the tube bundle (2) using a brush.
Check the integrity and cleanliness of the turbulators (3), if any; in general gaseous fuels should not pro-
duce any carbon deposit while with the use of liquid fuels, it is necessary to clean frequently to avoid
substantial fouling.
To clean more thoroughly, the smoke chamber is to be removed; in this way, carbon residues can be
eliminated from the back.
Check the integrity of the electrical system on the generator.
Check the integrity of the electrical panel, both outside (IP protection) and inside (check of all compo-
nents inside the electrical panel).
Periodically check the efficiency of adjusting and system safety tools.