Installation
19
BURNER ASSEMBLY
Having chosen the burner to be used, refer to the Manual supplied with it for information about:
–
the installation and fastening to the boiler
–
the connection to the fuel supply
–
the electrical connections
–
the adjustments to be made
–
maintenance
–
the necessary checks.
m
IMPORTANT
The insulating mat supplied as standard with the generator must be wrapped around the nosepiece for at least one full
turn in order to protect the burner flange from the flame. The insulating mat does not need to fill the gap up to the door
insulation inner surface. If the material supplied is not suitable for the burner used, use another material that can also
resist to 1000°C and whose size is appropriate to fully close the gap.
2
P6
5
Øb
4
3
1
1
2
1
Burner
2
Flange
3
Gasket
4
Door
5
Insulating mat
m
IMPORTANT
For fuel oil/biogas operation, the door should have concrete insulation and be equipped with suitable tie-rods. Any
changes and/or failure to disclose information during sales will void the warranty conditions.
ELECTRICAL CONNECTIONS
The electric system of a heating plant room used only to heat the buildings must be made by an authorised company that must
comply with regulations, some of which are general while others are specific for the single types of use or combustion.
m
IMPORTANT
Connect the earth cable to an effective earthing system.
ICI CALDAIE S.p.A.
is not liable for any damage caused by the
lack of the earthing system and the failure to comply with the instructions of the wiring diagrams.
d
PROHIBITION
Do not use the water and heating system pipes for the
earthing connections
.
Cooke Industries - Phone: +64 9 579 2185 Email: [email protected] Web: www.cookeindustries.co.nz