FAN 2 tests just as FAN 1. Pause for 3 seconds. 
 
FAN 1 and 2 test simultaneously as above. Pause for 3 seconds. 
 
ALARM relay activates for 3 seconds. Then system returns to normal operation. 
 

Operation 

The Ice Qube fan speed controller has two adjustable set points, one for the ambient fan and one for the 
enclosure fan. The ambient fan (FAN 2) set point has a range of 70°F to 110°F. It is set at 90°F from the 
factory. The enclosure fan (FAN 1) set point has a range of 50°F to 90°F. It is set at 70°F from the factory. 
 
Each fan also has an adjustable top speed differential. The fan will begin to operate at approximately 10% 
rated speed when the enclosure temperature is at its set point. The fan will ramp up to 100% when the 
temperature is 5°, 10°, 15° or 20°F above the selected set point. This differential is selected using the four 
dip switches located on the fan speed controller. Dip switches 1 and 2 control the enclosure fan (FAN 1), 
and dip switches 3 and 4 control the ambient fan (FAN 2). The differential for both fans is set at 10°F from 
the factory. 

Differential 

5° 

Off  Off  Off  Off 

10° 

Off 

On 

Off 

On 

15° 

On 

Off 

On 

Off 

20° 

On 

On 

On 

On 

 
Each fan has an LED that will indicate the status of the fans. Normally, with power supplied to the 
controller and the fans not operating, the LED’s will blink at a rate of 1 pulse every 2 seconds. When the 
fans begin to operate; the LED’s will blink 1 pulse per second. As the fan speed increases the LED blink 
speed will increase. 
 
Note: Single speed fans will start and immediately ramp to full speed. However, the LED will blink faster 
as temperature increases. The rate of pulse increase is dependent on the dip switch settings. 
 
Fan off temperature will be approximately 5°F (3°C) below fan on setting. 
 

Fan Failure Alarm 

A fan failure is displayed by a continuously lit LED. This alarm is not available for single speed fans and 
will not activate the alarm relay. 
 

Optional High Temperature Alarm: 

An alarm relay can provide a high temperature signal through either normally open (NO) or normally 
closed (NC) dry contacts. The high temperature alarm relay activation will be by default determined by: 
Fan 2 Tempe Dip Switch S 10°F 
 
The alarm will automatically reset when the temperature decreases 10°F. 

 

 

Содержание IQ10000HE

Страница 1: ...Nonhazardous Locations OPERATION AND INSTALLATION MANUAL IMPORTANT PLEASE READ this manual and follow the instructions for safe and satisfactory installation and operation of this system Keep this ma...

Страница 2: ...9 Fan Speed Controller Ord Loc Only 9 Maintenance 11 Trouble Shooting 11 Schematic Wiring Diagram 13 Specification Drawings 14 IQ700HE 14 IQ800HE 15 IQ900HE 16 IQ2200HE 17 IQ6100HE 18 IQ7400HE 19 IQ10...

Страница 3: ...veral systems that function simultaneously to maintain environmentally friendly conditions for your equipment within the enclosure The three main thermal related systems that we employ are the closed...

Страница 4: ...changer will be 1 Operation manual 2 Mounting hardware 3 Standard master warranty 4 Enclosure gasket Storage The storage space temperature should be in the range of 40 to 85 C 40 to 185 F in a non con...

Страница 5: ...point Factory set points Enclosure 70 F Ambient 90 F Fan speed controller option available for Ord Loc Only 4 After completing the above check point the Ice Qube TMS is ready to be mounted to your enc...

Страница 6: ...unting studs through the 3 8 9 5mm or 1 2 12 7mm depending on model holes in your enclosure and check to see that all openings are aligned 3 After checking that all openings and bolt holes are in alig...

Страница 7: ...heck that wire routing to the terminal box will not interfere with or become damaged by other components Electrical Installation 1 Check that the heat exchanger designated power supply is de energized...

Страница 8: ...8 Rev 6 Figure 3 Terminal Cover Figure 4 Terminal Block optional...

Страница 9: ...e or hot and is negative or neutral the power connection is polarity sensitive Be careful when handling or adjusting the controller as all components and circuitry are at line voltage except for the a...

Страница 10: ...s set at 10 F from the factory Differential 1 2 3 5 5 Off Off Off Off 10 Off On Off On 15 On Off On Off 20 On On On On Each fan has an LED that will indicate the status of the fans Normally with power...

Страница 11: ...xcess water from the filter before returning it to the system Replace the filter if it shows signs of deterioration See website for air filter cleaning demonstration at http www iceqube com ice qube t...

Страница 12: ...rating Yes No Is the enclosure door closed tightly Yes No Are all of the gaskets in place Yes No Has the ambient warm air stream filter been cleaned or changed recently If applicable Yes No Is the sys...

Страница 13: ...13 Schematic Wiring Diagram Figure 6...

Страница 14: ...14 Rev 6 Specification Drawings IQ700HE Figure 7...

Страница 15: ...15 Rev 6 IQ800HE Figure 8...

Страница 16: ...16 Rev 6 IQ900HE Figure 9...

Страница 17: ...17 Rev 6 IQ2200HE Figure 10...

Страница 18: ...18 Rev 6 IQ6100HE Figure 11...

Страница 19: ...19 Rev 6 IQ7400HE Figure 12...

Страница 20: ...20 Rev 6 IQ10000HE Figure 13...

Страница 21: ...21 Rev 6 Gasket and Cutouts IQ700 800HE Gasket and Cutout Same Gasket and Cutout for IQ700HE and IQ800HE Figure 14...

Страница 22: ...22 Rev 6 IQ900HE Gasket and Cutout Figure 15...

Страница 23: ...23 Rev 6 IQ2200HE Gasket and Cutout Figure 16...

Страница 24: ...24 Rev 6 IQ6100HE Gasket and Cutout Figure 17...

Страница 25: ...25 Rev 6 IQ7400HE Gasket and Cutout Figure 18...

Страница 26: ...26 Rev 6 IQ10000HE Gasket and Cutout Figure 19...

Страница 27: ...ility or any other theory of liability will be limited to the lesser of customer s actual damages or the price paid by customer to Ice Qube for the Products not including applicable taxes duties and f...

Страница 28: ...es be deemed to be non binding Such advice does not relieve customer from the obligation and customer accepts full responsibility to confirm for itself the suitability of the Products for their intend...

Страница 29: ...29 Rev 6 Notes...

Отзывы: