Instruction Manual – NPS914 Alarm and Indication IED
Setting the analog change deadbands
Table. 7.1.7. - 13. Analog change deadband settings.
Name
Range
Step
Default
Description
General deadband
0.1…10.0 %
0.1 %
2 %
Determines the general data reporting deadband settings.
Active energy deadband
0.1…1000.0
kWh
0.1
kWh
2 kWh
Determines the data reporting deadband settings for this
measurement.
Reactive
energy deadband
0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Active power deadband
0.1…1000.0
kW
0.1
kW
2 kW
Determines the data reporting deadband settings for this
measurement.
Reactive
power deadband
0.1…1000.0
kVar
0.1
kVar
2 kVar
Determines the data reporting deadband settings for this
measurement.
Apparent
power deadband
0.1…1000.0
kVA
0.1
kVA
2 kVA
Determines the data reporting deadband settings for this
measurement.
Power factor deadband
0.01…0.99
0.01
0.05
Determines the data reporting deadband settings for this
measurement.
Frequency deadband
0.01…1.00 Hz
0.01
Hz
0.1 Hz
Determines the data reporting deadband settings for this
measurement.
Current deadband
0.01…50.00 A
0.01 A
5 A
Determines the data reporting deadband settings for this
measurement.
Residual
current deadband
0.01…50.00 A
0.01 A
0.2 A
Determines the data reporting deadband settings for this
measurement.
Voltage deadband
0.01…5000.00
V
0.01 V
200 V
Determines the data reporting deadband settings for this
measurement.
Residual
voltage deadband
0.01…5000.00
V
0.01 V
200 V
Determines the data reporting deadband settings for this
measurement.
Angle
measurement deadband
0.1…5.0 deg
0.1
deg
1 deg
Determines the data reporting deadband settings for this
measurement.
Integration time
0…10 000 ms 1 ms
-
Displays the integration time of the protocol.