Reference: A938
Index: B
Page 55
This document is the property of ICE SAS. It can not be reproduced or communicated to third parties without authorization.
Instruction Manual – NPS914 Alarm and Indication IED
Name
Range
Step
Default
Description
Objectx
Withdraw
status
0:
WDIntermediat
e 1:
WDCartOut
2: WDCart In
3: WDBad
4: Not in use
-
-
Displays the status of circuit breaker cart. WDIntermediate is displayed
when neither of the status signals (in or out) are active. WDBad status
is displayed when both status signals (in and out) are active. If the
selected object type is not set to "Withdrawable circuit breaker", this
setting displays the "No in use" option
.
Additional
status
information
0: Open
Blocke
d
1:
Open
Allowed
2:
Close
Blocke
d
3:
Close
Allowed
4: Object Ready
5: Object Not
Ready
6: Sync Ok
7: Sync Not Ok
-
-
Displays additional information about the status of the object.
Use
Synchrochec
k
0: Not in
use 1:
Synchrochec
k in use
-
0: Not
in use
Selects whether the "Synchrocheck" condition is in use for the circuit
breaker close command. If "In use" is selected the input chosen to
"Sync.check status in" has to be active to be able to close circuit
breaker.
Use Object
ready
0: Ready High
1: Ready Low
2: Not in use
-
2: Not
in use
Selects whether the "Object ready" condition is in use for the circuit
breaker close command. If in use the signal connected to "Object ready
status In" has to be high or low to be able to close the breaker
(depending on "Ready High or Low" selection).
Open
requests
0…2
32
–1
1
-
Displays the number of successful "Open" requests.
Close
requests
0…2
32
–1
1
-
Displays the number of successful "Close" requests.
Open
requests
failed
0…2
32
–1
1
-
Displays the number of failed "Open" requests.
Close
requests
failed
0…2
32
–1
1
-
Displays the number of failed "Close" requests.
Clear
statistics
0: -
1: Clear
-
0: -
Clears the request statistics, setting them back to zero (0).
Automatically returns to "-" after the clearing is finished.