ELEVATION SERIES CIM CUBERS
SEQUENCE OF OPERATIONS
21
CONTROL BOARD - HARVEST
After the Water Inlet Valve closes following the 20 second time out, the Hot Gas Valve and Harvest Assist
will remain energized until the ice slab is harvested from the Evaporator. At this point the unit is reading
the Curtain Switch (s) and/or Bin Thermostat (if added).