REV. N
NeoGCP
i7
PLUS+
- 56 -
Items
Alarm Level
Delay
Time
Sequence Applied
Not
use
Warning
Trip
Stop
Shutdown
USER PRESS 1
LOW
○
○
○
○
○
2s
RUNNING ~
COOLDOWN
User Temperature 1 detected lower than set value
USER PRESS 1
SENSOR
◎
5s
Always
User Pressure 1 sensor not connected
USER PRESS 2
HIGH
○
○
○
○
○
2s
RUNNING ~
COOLDOWN
User Pressure 2 detected higher than set value
USER PRESS 2
LOW
○
○
○
○
○
2s
RUNNING ~
COOLDOWN
User Pressure 2 detected lower than set value
USER PRESS 2
SENSOR
◎
5s
Always
User pressure 2 sensor not connected
COOLANT LEVEL
HIGH
○
○
○
○
○
10s
Always
Coolant Level detected higher than set value
COOLANT LEVEL
LOW
○
○
○
○
○
10s
Always
Coolant Level detected lower than set value
COOLANT LEVEL
SENSOR
◎
5s
Always
Coolant Level sensor not connected
※ ◎ : Fixed item ○ : Optional item