GEN BREAKER
FAILURE
◎
0[s]
Always
When Breaker Close output occurs and then Breaker Aux contact is not input
※ ◎ : Fixed item ○ : Optional item
Engine Related Fault Items
17.2.
Items
Alarm Level
Delay
Time
Sequence applied
Not use Warning Trip
Stop Shutdown
OVER SPEED
○
○
○
○
○
Setup
Always
RPM detected higher than set value
UNDER SPEED
○
○
○
○
○
Setup
RUNNING
RPM detected lower than set value
EM’CY STOP
◎
◎
0[s]
Always
Emergency Stop input
FAIL TO START
◎
◎
0[s]
CRANK-ON
Crank Attempts expire in Auto Mode & Fire-Run Mode
FAIL TO STOP
◎
◎
2[s]
PRE-CRANK
Fail to Stop input
FAIL TO
STOP(RPM)
○
○
○
○
○
2[s]
PRE-CRANK
RPM detected higher than RUN-STATE RPM
FAIL TO STOP(OP
GAUGE)
○
○
○
○
○
2[s]
PRE-CRANK
Oil Pressure detected higher than RUN-STATE OP-GAUGE
FAIL TO STOP(OP
SWITCH)
○
○
○
○
○
2[s]
PRE-CRANK
No input of Oil Pressure S/W
COOLANT TEMP
S/W
○
○
○
○
○
Setup
BUILD-UP ~
COOLDOWN
Coolant Temp S/W input
OIL PRESS S/W
○
○
○
○
○
Setup
BUILD-UP ~
COOLDOWN
Oil Press S/W input
NO CHARGING
S/W
○
○
○
○
○
Setup
RUNNING
No Charging S/W input
COOLANT LEVEL
S/W
○
○
○
○
○
Setup
Always
Coolant Level S/W input
BAT VOLTAGE
HIGH
○
○
○
○
○
10[s]
Always
Battery Voltage detected higher than set value.
BAT VOLTAGE
LOW
○
○
○
○
○
10[s]
Always
Battery Voltage detected lower than set value.
MPU FAILURE
◎
5[s]
BUILD-UP ~
COOLDOWN
When using RPM measurement method as MPU and RPM is detected 0
※ ◎ : Fixed item ○ : Optional item