NeoGCP
i7
PLUS+
- 28 -
Menus that are influenced
Setup
[SYSTEM] → [VOLTAGE]
6600 [V]
[SYSTEM] → [PT RATIO]
60.0 (= 6600/110)
CT RATIO (CT)
7.10.
- Setup CT(Current Transformer) Ratio.
- Setup : 5/5 ~ 9999/5 [A]
GR CT RATIO (ZCT)
7.11.
- Setup ZCT(Zero Current Transformer)Ratio.
- Setup : 5/5 ~ 9999/5 [A]
RPM (RPM)
7.12.
- Setup Gen-set RPM.
- Setup : 0 ~ 4000 [RPM]
GOVERNOR TYPE (GOV)
7.13.
- Setup Governor Type.
- Setup : FUEL, STOP
Menus that are influenced
Setup
[DO-CONFIG]
[C_GOVERNOR] port set by user
TEETH(FACTOR)(TEETH)
7.14.
- Setup engine gear Teeth.
- Setup : 0 ~ 250
Set value
Description
31 ~ 250
Use MPU as RPM measurement type
20
Use voltage as RPM measurement type in 6-
pole generator
30
Use voltage as RPM measurement type in 4-
pole generator
7.15.
BREAKER TYPE (TYPE)
7.15.1.
- Setup Breaker Type
- Setup : MCCB, ACB, MC