- When using EP20, additional contact input setup is possible as shown below.
Menus that are influenced
Setup
Description
[SYSTEM] → [EXT-MODULE]
EP20
When using EP20
[DI-CONFIG] → From [DI 11 SET]
Relevant
contact
Oil Press S/W LH
Oil Press S/W RH
Coolant S/W LH
Coolant S/W RH
Oil temp S/W
USER FAULT
9.1.
- Used as user fault contact.
- When contact is input, operation mode of Gen-set will switch according to set alarm level after set delay
time.
- Alarm message can be revised.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level), MESSAGE(TEXT)
USER FAULT(RUN)
9.2.
- Used as user fault contact in [RUN].
- When contact is input, operation mode of Gen-set will switch according to set alarm level after set delay
time.
- Alarm message can be revised.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level), MESSAGE(TEXT)
USER FAULT(STOP)
9.3.
- Used as user fault contact in [READY].
- When contact is input, operation mode of Gen-set will switch according to set alarm level after set delay
time.
- Alarm message can be revised.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level), MESSAGE(TEXT)
EM’CY STOP S/W
9.4.
- Used as Emergency stop switch contact.
- When contact is input, Gen-set will shut down.
- Setup : TYPE(N/O, N/C), DELAY(0.0 ~ 25.0[s]), ALARM LEVEL(7level), MESSAGE(TEXT)