Height
Width
Depth
Maximum weight
44 mm
(1.73 in.)
439 mm
(17.3 in.)
579 mm
(22.8 in.)
16 kg
(35.3 lb)
Note:
The 2145 UPS-1U package, which includes support rails, weighs 18.8 kg (41.4 lb).
Heat output
The 2145 UPS-1U unit produces the following approximate heat output.
Model
Heat output during normal
operation
Heat output during battery
operation
2145 UPS-1U
10 W (34 Btu per hour)
150 W (512 Btu per hour)
Power cables for the 2145 UPS-1U
If you do not connect the 2145 UPS-1U to a rack power-distribution unit (PDU) or
redundant ac-power switch, you must follow your country or region’s power
requirements to choose the appropriate power cable for the 2145 UPS-1U.
The 2145 UPS-1U is supplied with an IEC 320-C13 to C14 jumper to connect it to a
rack PDU. You can also use this cable to connect the 2145 UPS-1U to the redundant
ac-power switch.
The following table lists the power cable options for your country or region.
Country or region
Length
Connection type
(attached plug
designed for 200
- 240 V ac
input)
Part number
United States of America (Chicago),
Canada, Mexico
1.8 m (6 ft)
NEMA L6-15P
39M5115
Bahamas, Barbados, Bermuda,
Bolivia, Brazil, Canada, Cayman
Islands, Colombia, Costa Rica,
Dominican Republic, Ecuador, El
Salvador, Guatemala, Guyana, Haiti,
Honduras, Jamaica, Japan, Korea
(South), Liberia, Mexico,
Netherlands Antilles, Nicaragua,
Panama, Peru, Philippines, Saudi
Arabia, Suriname, Taiwan, Trinidad
(West Indies), United States of
America, Venezuela
2.8 m (9 ft)
NEMA L6-15P
39M5116
Appendix B. SAN Volume Controller physical installation planning
45
Содержание SAN Volume Controller 2145-CF8
Страница 2: ......
Страница 8: ...vi IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide...
Страница 10: ...viii IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide...
Страница 16: ...xiv IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide...
Страница 26: ...xxiv IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide...
Страница 32: ...6 IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide...
Страница 64: ...38 IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide...
Страница 66: ...40 IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide...
Страница 92: ...66 IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide...
Страница 99: ......
Страница 100: ...Part Number 31P1135 Printed in USA GC52 1356 01 1P P N 31P1135...
Страница 101: ...Spine information IBM System Storage SAN Volume Controller Model 2145 CF8 Hardware Installation Guide Version 5 1 0...