14
IBM System p5 550 and 550Q Technical Overview and Introduction
1.5.1 IBM 7014 Model T00 Rack
The 1.8-meter (71-inch) Model T00 is compatible with past and present IBM System p
servers. It is a 19-inch rack and is designed for use in all situations that have used the earlier
rack models R00 and S00 previously. The T00 rack has the following features:
36 EIA units (36U) of usable space.
Optional removable side panels.
Optional highly perforated front door.
Optional side-to-side mounting hardware for joining multiple racks.
Standard business black or optional white color in OEM format.
Increased power distribution and weight capacity.
Optional reinforced (ruggedized) rack feature (FC 6080) provides added earthquake
protection with modular rear brace, concrete floor bolt-down hardware, and bolt-in steel
front filler panels.
Support for both ac and dc configurations.
The dc rack height is increased to 1926 mm (75.8 in.) if a power distribution panel is fixed
to the top of the rack.
Up to four power distribution units (PDUs) can be mounted in the PDU bays (see
Figure 1-4 on page 18). Additional PDUs can fit inside the rack (see 1.5.6, “The ac power
distribution unit and rack content” on page 17).
Weights:
– T00 base empty rack: 244 kg (535 lb.)
– T00 full rack: 816 kg (1795 lb.)
Optional power distribution panel
The 7014-T00 rack Power Distribution Panel (PDP) feature code 6117 provides attachment
for up to four 5-pin to 5-pin PDP power cables (p5-550 or p5-550Q FC 6688). This allows a
maximum of up to two p5-550 or p5-550Q with redundant dc power supplies or up to four
p5-550 or p5-550Q without redundant dc power supplies.
To mount more than two p5-550 or p5-550Q with redundant dc power supplies in a rack,
FC 0986 must be specified so the configuration receives special request services from the
Center for Customized Solutions.
Rack FC 6117 provides the proper capacity circuit breakers for use with the p5-550 or
p5-550Q based on the inclusion of rack FC 0230 (Rack Content Specify, 9133-55A) on the
7014-T00 rack order.
Note: It is the client’s responsibility to ensure that the installation of the drawer in the
preferred rack or cabinet results in a configuration that is stable, serviceable, safe, and
compatible with the drawer requirements for power, cooling, cable management, weight,
and rail security.
Содержание p5 550
Страница 2: ......
Страница 8: ...vi IBM System p5 550 and 550Q Technical Overview and Introduction...
Страница 14: ...xii IBM System p5 550 and 550Q Technical Overview and Introduction...
Страница 38: ...24 IBM System p5 550 and 550Q Technical Overview and Introduction...
Страница 90: ...76 IBM System p5 550 and 550Q Technical Overview and Introduction...
Страница 104: ...90 IBM System p5 550 and 550Q Technical Overview and Introduction...
Страница 108: ...94 IBM System p5 550 and 550Q Technical Overview and Introduction...
Страница 109: ......