Table 7. Power consumption examples per enclosure
Model and type PSU
Input power
requirements
Maximum
input current
Maximum
power output
(W)
Caloric value
(BTU/hr)
5147-092
expansion
enclosure with
92 HDDs in a
primary
enclosure. 2
SSDs and 90
HDDs in non-
primary
enclosures,
3.5-inch form
factor SAS drive
slots
1200 W (2)
180 V to 264 V
single phase AC
at a frequency
of 47 Hz to 63
Hz
6.12 A
Requires a C20
power socket
(C20 PDU)
1200
4096
Note: These measurements are presented as an example. Measurements that are obtained in other
operating environments might vary. Conduct your own testing to determine specific measurements for
your environment.
Each Model 092 expansion enclosure contains two PSUs for redundancy. The total power consumption
values represent the total power that is drawn by both PSUs.
Environmental requirements
System airflow is from the front to the rear of each enclosure:
• Airflow passes between drive carriers and through each enclosure.
• The combined power and cooling module exhausts air from the rear of each canister.
Ensure that your environment falls within the ranges that are listed in Table 8 on page 28.
Table 8. Temperature requirements
Environment
Ambient temperature
Altitude
Relative humidity
Operating
5°C to 32°C
1
(41°F to 90°F)
0 - 3048 m
2, 3
(0 - 10000 ft)
8% to 80% non-
condensing
Non-operating
1°C to 50°C
(34°F to 122°F)
-305 to 12192 m
(-1000 to 40000 ft)
8% to 80% non-
condensing
Storage
1°C to 60°C
(34°F to 140°F)
5% to 80% non-
condensing
Shipping
-40°C to 60°C
(-40°F to 140°F)
5% to 100% condensing,
but not precipitating
Note:
• – Max Ambient Temperature Environment = 32C / 950 m
– Max Altitude Environment = 25C / 3,050 m
– Decrease the maximum air temperature by 1 degree C per 300 m above 950 m.
• The maximum ambient operating temperature when using an optical cable or discrete optical
transceiver is 32C, which includes all Ethernet (100Gb) cables and InfiniBand (100Gb EDR) that are
28 IBM Elastic Storage System 5000: Model 092 Hardware Guide
Содержание Elastic Storage System 5000 Series
Страница 1: ...IBM Elastic Storage System 5000 Version 6 0 1 Model 092 Hardware Guide IBM SC28 3135 00...
Страница 8: ...viii...
Страница 10: ...24 Enclosure models and rack requirements 74 x...
Страница 14: ...xiv IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 32: ...18 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 36: ...22 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 51: ...Figure 11 Cable connectivity from I O servers Chapter 4 Planning for hardware 37...
Страница 86: ...72 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 90: ...76 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 98: ...84 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 100: ...86 IBM Elastic Storage System 5000 Model 092 Hardware Guide...
Страница 101: ......
Страница 102: ...IBM Product Number 5765 DME 5765 DAE SC28 3135 00...