Dual latch rail tray
To remove a sliding tray with dual latch rails:
1. Power-off the rack.
2. Open the rear door of the rack cabinet and remove the pin
1
that secures the
sliding tray to the cable management arm.
3. Loosen the thumbscrews
2
on the sliding tray and fully extend the sliding tray.
4. Push in on the spring of the right rear locking tab
3
and push the sliding tray
approximately two inches into the cabinet.
5. Release both left and right forward locking tabs
4
. Then, while holding the
sliding tray in place, push both left and right outside sliding rails
5
into the
rack cabinet until it disconnects from the sliding tray.
Note:
Left side view for
4
and
5
are not shown.
Sliding rails
This procedure is for single latch sliding rails and dual latch sliding rails.
For single latch sliding rails, the right rail is the one that has the front latch. The left
rail does not have a front latch.
For dual latch sliding rails, the right rail is the one that has the rear latch. The left
rail does not have a rear latch.
To remove the sliding rails:
1. Power-off the rack.
2. Remove the sliding tray that is attached to the sliding rails that you want to
remove. See “Sliding trays” on page 45.
3. Use a 3/32-inch allen wrench to remove the four screws that secure each of the
sliding rails to the rack cabinet.
46
Hardware Maintenance Manual: IBM PC Server/Enterprise Racks Types 9306, 9308
Содержание 9306
Страница 1: ...Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 2: ......
Страница 3: ...Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 10: ...viii Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 14: ...4 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 19: ...Figure 4 Expansion NetBAY42 Rack cabinet without side panels Type 9306 Model 250 420 421 9...
Страница 40: ...30 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 64: ...54 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 66: ...Primary Rack Model 42P 56 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 67: ...Extension Rack Model 42X NetBAY 42 Enterprise Rack Type 9308 Models 42P 42X 4SA 4SB 42S 42E 57...
Страница 68: ...Primary Rack 42S 58 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 84: ...Foot pads Front cover 74 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 87: ...Note The maximum server weight is 77 kg 170 lb NetBAY3 enclosure 77...
Страница 90: ...Front cover 80 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 94: ...84 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 108: ...98 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 109: ...Parts listing Type 9306 Model OPT 1 2 2 3 1U Flat Panel Monitor Console Kit 99...
Страница 117: ...Rear of rail UPS UPS screws Front of rail Figure 28 Installing a UPS Installing Optional Devices 107...
Страница 177: ...Figure 72 Connecting and routing other power cables to the outlets Installing Optional Devices 167...
Страница 184: ...Blank bezel Fixed shelf 174 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 200: ...190 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 203: ...1 DANGER 2 DANGER 3 DANGER 4 DANGER Related service information 193...
Страница 207: ...1 2 3 4 Related service information 197...
Страница 215: ...Related service information 205...
Страница 216: ...206 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 217: ...Related service information 207...
Страница 218: ...208 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 219: ...Related service information 209...
Страница 220: ...210 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 221: ...Related service information 211...
Страница 231: ...Related service information 221...
Страница 232: ...222 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 233: ...Related service information 223...
Страница 234: ...224 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 235: ...Related service information 225...
Страница 236: ...226 Hardware Maintenance Manual IBM PC Server Enterprise Racks Types 9306 9308...
Страница 243: ......
Страница 244: ...Part Number 10K2658 1P P N 10K2658...