background image

9.

Install a screw and washer into all four positions, but do not tighten.

10.

After all racks are bolted together, level the racks.

11.

Tighten all four screws.

12.

Snap on the trim pieces that go between the front and back racks.

13.

Snap on the trim piece that goes on top and between the racks.

14.

Install rack filler panels to cover the open areas at the front of the racks. All the gaps in the front of
the rack must also be sealed, including the gaps between equipment. This step ensures that proper
airflow within the rack is maintained.

15.

Connect the cables that go between the racks.

16.

If you are installing tip plates, go to step 5 in “Installing the rack” on page 1.

Removing and replacing the rack top cover

You might need to remove or replace the rack top cover. User these procedures to perform these tasks.

Removing the rack top cover:

You might need to remove the rack top cover. Use this procedure to perform this task.

Note:

A 10 mm box socket with an extension bar is required to remove the screws from the top cover.

Other tools might cause the screw heads to become rounded and unremovable.

To remove the rack cover from the rack, complete the following steps:

1.

Remove the front door.

Note:

If the rack is locked, unlock the doors. Then unlock the side panels by removing the locking

bars from both sides of the top rear of the rack. Slide the locking bars out from the rack at the top of
each side of the rack from the rear. The locking bars can be removed from each side of the front of the
rack if the rack space in the locking bars area is open and the bars are easily accessible.

2.

Remove the top, left, and right trim panels.

3.

Remove the side panels. For more information, see “Removing and replacing 7014-T00 or 7014-T42
side panels” on page 21.

4.

Remove one screw from the right side of the top cover and one screw from the left side of the top
cover. Do for both front and rear covers.

5.

Locate the front

(A)

and back

(C)

rack braces that were provided in the shipping container. Fasten

each rack brace at the top of the front and rear of the rack, just below the top cover.

6.

Use the four screws

(B)

that were removed from the top cover to secure each rack brace to the rack,

as shown in Figure 34 on page 36.

Racks and rack features

35

Содержание 7014-T42

Страница 1: ...Power Systems Racks and rack features ...

Страница 2: ......

Страница 3: ...Power Systems Racks and rack features ...

Страница 4: ... Notices manual G229 9054 and the IBM Environmental Notices and User Guide Z125 5823 This edition applies to IBM Power Systems servers that contain the POWER7 processor and to all associated models Copyright IBM Corporation 2010 2013 US Government Users Restricted Rights Use duplication or disclosure restricted by GSA ADP Schedule Contract with IBM Corp ...

Страница 5: ...r 7014 T42 side panel 22 Removing and replacing 7014 T00 or 7014 T42 trim panels 22 Removing the 7014 T00 or 7014 T42 trim panels 22 Replacing the 7014 T00 or 7014 T42 trim panels 23 Attaching the rack doors 24 Attaching a high perforation front door 25 Rack safety notices 26 Installing the rack security kit 28 Ruggedized kit 30 Releasing the ruggedized brace 31 Releasing the side panel with a rug...

Страница 6: ...iv Power Systems Racks and rack features ...

Страница 7: ...uct The documentation contains the safety information in your national language with references to the U S English source Before using a U S English publication to install operate or service this product you must first become familiar with the related safety information documentation You should also refer to the safety information documentation any time you do not clearly understand any safety inf...

Страница 8: ...equipment that will be attached to this product to properly wired outlets v When possible use one hand only to connect or disconnect signal cables v Never turn on any equipment when there is evidence of fire water or structural damage v Disconnect the attached power cords telecommunications systems networks and modems before you open the device covers unless instructed otherwise in the installatio...

Страница 9: ...he customer to ensure that the outlet is correctly wired and grounded to prevent an electrical shock CAUTION v Do not install a unit in a rack where the internal rack ambient temperatures will exceed the manufacturer s recommended ambient temperature for all your rack mounted devices v Do not install a unit in a rack where the air flow is compromised Ensure that air flow is not blocked or reduced ...

Страница 10: ...choose can support the weight of the loaded rack cabinet Refer to the documentation that comes with your rack cabinet for the weight of a loaded rack cabinet v Verify that all door openings are at least 760 x 230 mm 30 x 80 in v Ensure that all devices shelves drawers doors and cables are secure v Ensure that the four leveling pads are raised to their highest position v Ensure that there is no sta...

Страница 11: ... This product might contain one or more of the following devices CD ROM drive DVD ROM drive DVD RAM drive or laser module which are Class 1 laser products Note the following information v Do not remove the covers Removing the covers of the laser product could result in exposure to hazardous laser radiation There are no serviceable parts inside the device v Use of the controls or adjustments or per...

Страница 12: ...Power and cabling information for NEBS Network Equipment Building System GR 1089 CORE The following comments apply to the IBM servers that have been designated as conforming to NEBS Network Equipment Building System GR 1089 CORE The equipment is suitable for installation in the following v Network telecommunications facilities v Locations where the NEC National Electrical Code applies The intrabui...

Страница 13: ... PDU models v Topic collections that included installation information for servers expansion units and disk drive enclosures now provide links to the same information in applicable model specific sections For servers see the installation topics contained in each system model topic For expansion units and disk drive enclosures see model specific installation topics in Enclosures and expansion units...

Страница 14: ...rectory of worldwide contacts Country region for contact information for your country v IBM Rochester Manufacturing Automated Information Line at 1 800 300 8751 United States only Positioning the rack Proper rack positioning is needed to comply with safety and regulatory requirements Use the procedure in this section to perform this task After the rack has been placed into its location on the floo...

Страница 15: ...ching the stabilizer brackets You might need to attach the stabilizer brackets to the rack This section helps you determine whether stabilizer brackets are necessary and describes how to attach them if needed If the front or back ac electrical outlets are going to be installed in the rack you cannot attach the stabilizer brackets The rack must be bolted to the floor Stabilizer brackets are used on...

Страница 16: ...ets in the rack the rack must be bolted to the floor This section describes how to perform this task for a concrete floor Obtain the services of a mechanical contractor to attach the rack mounting plates to the concrete floor The mechanical contractor must determine that the hardware being used to secure the rack mounting plates to the concrete floor is sufficient to meet the requirements for the ...

Страница 17: ...e the hardware mounting kit and the two mounting plates Refer to the following illustration when reviewing the contents of the hardware mounting kit The hardware mounting kit contains the following items v 4 Rack mounting bolts v 4 Thin washers v 8 Plastic isolator bushings v 4 Thick washers v 4 Spacers 5 If you are installing an ac powered rack temporarily install the lower plastic isolator bushi...

Страница 18: ...te mounting location under the rack 7 Create a rack mounting bolt assembly by adding the following items in the order listed to each rack mounting bolt a Thin washer b Top plastic isolator bushing c Thick flat washer d Spacer 8 Insert a rack mounting bolt assembly through each of the leveling feet 9 Reposition the rack mounting plates under the four rack mounting bolts so that the mounting bolts a...

Страница 19: ...the bottom isolator bushing from each of the leveling feet 15 Remove the stabilizer brackets from the marked locations 16 Loosen each of the locking screws on the casters 17 Move the rack so that it is clear of both areas that were marked on the floor for the stabilizer bracket locations 18 Reposition the stabilizer brackets within the marked areas 19 Mark the floor at the center of all holes in b...

Страница 20: ...concrete floor Note The size of the anchor bolts and concrete anchors must be determined by the mechanical contractor who will be installing the rack mounting plate 27 Position the rack over the stabilizer bracket 28 Insert each of the stabilizer bracket bolts through a flat washer a plastic isolator bushing and a thick washer and through a leveling foot 29 Align the four stabilizer brackets bolts...

Страница 21: ... the rack to a concrete floor which lays beneath a raised floor follow the procedure described in this section Obtain the services of a mechanical contractor to attach the rack mounting plates to the concrete floor The mechanical contractor needs to determine that the hardware being used to secure the rack mounting plates to the concrete floor is sufficient to meet the requirements for the install...

Страница 22: ...washers v Four spacers 5 If you are installing an ac powered rack temporarily install the lower plastic isolator bushings to help you locate the rack mounting plate After the mounting plate has been correctly located remove the lower plastic isolator bushings 1 Rack chassis 7 Jam nut 2 Rack mounting bolt 8 Leveling foot 3 Thin washer 9 Lower plastic isolator bushing used only on dc powered systems...

Страница 23: ...unting plate The drilled holes should be approximately 1 inch deep This depth will accommodate any rack mounting bolt extending past the rack mounting plate when securing the rack to the rack mounting plate 22 For each rack mounting plate select at least two suitable hole locations Select the hole locations as close to the threaded hole areas as possible Be sure the hole locations selected at the ...

Страница 24: ...lign the rack over the front and rear stabilizer brackets 33 Insert each of the bolt assemblies through a leveling foot 34 Align the rack mounting bolts with the threaded holes in each stabilizer bracket Turn each bolt three to four rotations 35 Tighten the locking screw on each caster 36 Adjust the leveling feet downward as needed until the rack is level When the rack is level tighten the jam nut...

Страница 25: ...nts are made with the receptacle faceplate in the usual installed position 2 Some receptacles are enclosed in metal housings For this type of receptacle complete the following steps a Using a multimeter check for less than 1 volt from the receptacle case to any grounded metal structure in the building such as a raised floor metal structure water pipe building steel or similar structure b Using a m...

Страница 26: ...ns of the related hardware components and shows how these components relate to each other If you do not want ac outlets installed on the rack go to Installing the ac outlet mounting plate without ac outlets on page 17 If you want ac outlets installed on the front or rear ac outlet mounting plate complete the following steps 1 Determine the number of ac outlets that you are installing 2 Confirm wit...

Страница 27: ...round cable 6 Long end of ground cable 12 Ground lug nut quantity 2 16 Position the rear ac outlet mounting plate onto the rack frame with the ground lug fully inserted through the mounting holes in the rack 17 Install the front ac outlet mounting plate screws stabilizer mounting screws into the mounting plate and through the mounting holes in the rack Securely tighten the screws 1 Front or rear o...

Страница 28: ... the rear ac outlet mounting plate screws stabilizer mounting screws into the mounting plate and through the mounting holes in the rack Securely tighten the screws Note The bus bar might be located at either the top or bottom of the rack 1 Bus bar mounting plate 3 Hex screws M5 x 20 quantity 2 2 Lock washer quantity 2 4 Ground bus bar Figure 12 Installing the front mounting plate Figure 13 Install...

Страница 29: ...can use the procedure in this section to perform this task This section also includes illustrations of the related hardware components and shows how these components relate to each other Note The customer is responsible for providing and connecting the 48 V dc power source and 48 V dc power return cables from the customer s source 48 V dc to the bus bars in the power distribution panel The custome...

Страница 30: ...he power source switches or fuses lock out tag out to indicate that the power source is turned off intentionally Note Ensure that any oxidation on the copper bus bars is removed c If this is a raised floor installation and you are working at the back of the rack route the power cables up the rack s right side d Ensure that the external 48 V dc power cable is connected correctly to the 48 V dc bus ...

Страница 31: ...terminal board on the back cover of the dc power distribution panel Note Ensure that you remove the oxidation on the copper bus bars g Ensure that the power source ground cable is routed correctly and connects the power source ground cable to the copper bar at the lower back or upper back center of the rack h If the rack is on a raised floor attach the 48 V dc power source cables to the rear of th...

Страница 32: ...d cable Install at either top or bottom of the rack 6 Reinstall the 48 V dc bus bar shield 7 Reinstall the top cover on the dc power distribution panel 8 Reinstall the cable channel cover 1 Cable channel cover Figure 17 Cable locations 20 Power Systems Racks and rack features ...

Страница 33: ... complete the following steps 1 Unlock the side panels by pressing down on both locking latches to release the latches Note If your rack uses a ruggedized kit you must remove the securing screw to allow each side panel to be removed See Releasing the side panel with a ruggedized kit on page 32 2 Tilt the top of the side panel slightly toward you 3 Lift the side panel away from the ridge on the bot...

Страница 34: ...ks that are installed with multiple processor drawer systems can use front trim panels instead of doors For racks that use trim panels a reduced interference panel type must be installed when certain expansion unit models are present Use the procedures in this section to remove the existing trim panels from the rack and replace them with the reduced interference panel type Removing the 7014 T00 or...

Страница 35: ...d set it aside 5 Repeat this procedure to remove the left side trim panel Replacing the 7014 T00 or 7014 T42 trim panels For racks that use trim panels instead of doors a reduced interference panel type must be installed when certain expansion unit models are present Use the procedure in this section to replace the trim panels To install the trim panels complete the following steps Figure 21 Remov...

Страница 36: ...hold the panel in place 4 Repeat this procedure to install the left side trim panel Attaching the rack doors Learn how to attach the rack doors Use this procedure to perform this task Depending on the model of the rack the front door of a rack might be an optional feature If your system already has the front door installed or does not have a front door to install skip this step Figure 22 Installin...

Страница 37: ...gh perforation front door complete the following steps 1 Read the Rack safety notices on page 26 2 Remove the top left and right trim panels For details about removing the left and right trim panels from a 7014 T00 or 7014 T42 rack see Removing and replacing 7014 T00 or 7014 T42 trim panels on page 22 Figure 23 Attaching the rack door Racks and rack features 25 ...

Страница 38: ...eed to read the rack safety notices before installing equipment Before installing a rack rack features or a system or expansion unit into a rack read the following safety information Attention If you are installing equipment into a non IBM rack the rack must comply with the Electronics Industries Association EIA 310D specifications If you do not have a rail kit designed for the equipment in the no...

Страница 39: ...er to ensure that the outlet is correctly wired and grounded to prevent an electrical shock CAUTION v Do not install a unit in a rack where the internal rack ambient temperatures will exceed the manufacturer s recommended ambient temperature for all your rack mounted devices v Do not install a unit in a rack where the air flow is compromised Ensure that air flow is not blocked or reduced on any si...

Страница 40: ...nd shows how these components relate to each other To install a rack security kit feature 6580 that consists of the security lock and security slide bars complete the following steps 1 Read the Rack safety notices on page 26 2 Verify the inventory in the rack security kit 1 Two lock hardware kits Each kit contains Rack lock Bracket Screw Two keys 2 Two security slide bars 28 Power Systems Racks an...

Страница 41: ...lock bracket 5 with the screw 4 on the inside of the door 5 Repeat steps 3 and 4 to install the second lock on the back rack door 6 Install a security slide bar on the right side of the rack Note Each slide bar rail has two long tabs on the bottom of the rail The slide bar rails are identical and can be installed on either the right or left side cover panel a Unlatch right side cover panel and lea...

Страница 42: ... the locked position the tab is over the locked symbol 11 as shown in Figure 28 and over the unlocked symbol 12 when the slide bar is unlocked f Repeat the procedure for the left side of the rack Ruggedized kit You might need to remove or replace a part in the ruggedized kit This section includes procedures so that you can perform these tasks Figure 27 Installing a security slide bar Figure 28 Pla...

Страница 43: ... need to uninstall and reinstall a part 1 Rack 9 Brace hinges 2 Spacer 10 Brace 3 Brace hinge 11 Side door securing screw mount 4 Hinge pivot studs 12 Spacer 5 Brace latch bracket 13 Screw 6 Spacer 14 Washer 7 Screw 15 Side door securing screw 8 Brace thumbscrew Releasing the ruggedized brace You might need to release the ruggedized brace Use the procedure in this section to perform this task To a...

Страница 44: ...his procedure to perform this task The ruggedized kit contains securing screws that secure the side panels to the rack To remove a securing screw complete the following steps 1 If necessary open or remove the back rack door 2 Locate the securing screw mount 11 for the side door that will be removed Figure 30 Releasing the brace to access systems 32 Power Systems Racks and rack features ...

Страница 45: ...ttachment kit feature 7840 To connect multiple racks with the rack to rack attachment kit complete the following steps 1 Read the Rack safety notices on page 26 2 If they are installed remove the side panels from each rack Remove side panels only from the sides that will be attached to each other by completing the following steps a Lift up the two panel release tabs b Pull the panel up and away fr...

Страница 46: ...foam as shown in Figure 32 For a model T42 rack join the short foam to the end of the long foam and adhere it to the frame length of the rack 7 Position the racks together 8 Align the standoff holes You might need to adjust the leveling feet to do this Figure 32 Removing the side panels Z and J brackets and installing standoffs and long foam to connect multiple racks Figure 33 Location of foam str...

Страница 47: ...cover Other tools might cause the screw heads to become rounded and unremovable To remove the rack cover from the rack complete the following steps 1 Remove the front door Note If the rack is locked unlock the doors Then unlock the side panels by removing the locking bars from both sides of the top rear of the rack Slide the locking bars out from the rack at the top of each side of the rack from t...

Страница 48: ... B Retaining screws 2 screws for each brace C Rear rack brace 7 Remove the remaining six screws from the left and right sides of the top cover D Figure 34 Securing the rack brace 36 Power Systems Racks and rack features ...

Страница 49: ...socket with an extension bar is required to replace the screws into the rack top cover Other tools might cause the screw heads to become rounded and unable to be removed again To replace the rack top cover onto the rack complete the following steps 1 Position the rack top cover D on the rack 2 Install the six screws at the left and right sides of the rack top cover Figure 35 Removing the top cover...

Страница 50: ...crews into the rack top cover Other tools might cause the screw heads to become rounded and unable to be removed again 3 Remove the rack braces A and C by unfastening them at the top of the rack just below the top cover Remove the braces at the front and rear of the rack Figure 36 Removing the top cover 38 Power Systems Racks and rack features ...

Страница 51: ...be installed in the 7014 T00 and 7014 T42 racks It allows you to monitor the individual power loads of the devices that are plugged into it Installing the PDU or PDU in the side of a rack Learn how to install the power distribution unit PDU or power distribution unit plus PDU vertically in the side of a rack Tip Removing the rack doors and side panels might make installation easier To install the ...

Страница 52: ...t Use screws that were provided with the rack mounting kit 5 Attach nut clips A to the four locations on the rack mounting flanges where the PDU model will be attached Use nut clips that were provided with the rack mounting kit See the following figure Figure 38 Aligning the vertical mounting brackets to the front of the PDU Figure 39 Attaching nut clips to the rack mounting flanges 40 Power Syste...

Страница 53: ...t the main input power before connecting or disconnecting the input power cord from the PDU model 7 If the PDU model was provided with a detached power cord connect the power cord now Align the connector on the power cord A that was provided with the PDU model with the connector on the front of the unit A turning as necessary for key alignment Then turn the connector twist lock B clockwise until i...

Страница 54: ...ncepts Setting up power monitoring using the PDU on page 45 You can monitor the power status for any device that is connected to the power distribution unit plus PDU either manually or remotely through the PDU web interface Installing the PDU or PDU horizontally in a rack Learn how to install the power distribution unit PDU or power distribution unit plus PDU horizontally in the side of a rack Tip...

Страница 55: ...h the rack mounting kit 6 Identify an open mounting space that is the size of a single EIA in the rack where you will install the PDU model At the front of the rack attach an M6 screw to the middle hole of the EIA on each side of the rack At the rear of the rack attach nut clips to the top and bottom holes of the EIA on each side of the rack Use nut clips that were provided with the rack mounting ...

Страница 56: ...es 8 Align the end of the PDU model with the short mounting brackets with the outside of the rack flanges Use two M6 screws A per bracket to attach the brackets to the nut clips or cage nuts on the rack flanges Use screws that were provided with the rack mounting kit 9 Secure the long mounting brackets and the blank filler panel A to the rack cabinet by completing the following steps a Adjust the ...

Страница 57: ...ard the back of the rack and secure the power cord with the cable straps that are provided with the PDU model 12 Route the power cord toward a dedicated power source Use the provided cable straps to secure the power cord along the way Use the openings in the rack if the power cord must exit the rack to connect to a power source Attention To prevent damage to a power device and other connected devi...

Страница 58: ...ms Accessories Communications HyperTerminal The Connection Description window is displayed 2 Type the name for the connection in the Name field and select an icon for the connection 3 Click OK The Connect To window is displayed 4 In the Connect using field select the COM port that is connected to the PDU 5 Click OK The Properties window is displayed 6 Click Restore Defaults to use the default sett...

Страница 59: ...Settings 2 Enter the menu option for Set the IP Address Gateway Address and MIB System Group Using the web interface to configure the PDU Learn how to use the web interface to configure and monitor the power distribution unit plus PDU remotely The PDU provides a graphical user interface that you can view from a web browser Using a web browser you can access and monitor the PDU power outlets and ou...

Страница 60: ...eb SNMP card You can view the PDU and Web SNMP card information on the Identification of Power Management page To view the power management information of the PDU and Web SNMP card complete the following steps 1 From the main status page in the left navigation pane click System 2 Click Identification to view the PDU and Web SNMP card information Adding users You can add users who can access and co...

Страница 61: ... view or change the network configuration of the PDU complete the following steps 1 From the main status page in the left navigation pane click Network 2 Click Configuration to set the PDU IP address gateway address subnet mask and Domain Name System DNS address 3 Click Control to configure TCP IP settings 4 Click Access Control to set access control to prevent unauthorized users from accessing th...

Страница 62: ...system For more information about planning and installing the IBM PureFlex System 42U Rack 7953 94X and the IBM 42U Slim Rack 7953 94Y see Installation Guide IBM 42U 1100 mm Enterprise V2 Dynamic Rack and Dynamic Expansion Rack and IBM PureFlex System 42U Rack and 42U Expansion Rack Types 7953 and 9363 50 Power Systems Racks and rack features ...

Страница 63: ...d or changes in the product s and or the program s described in this publication at any time without notice Any references in this information to websites not owned by the manufacturer are provided for convenience only and do not in any manner serve as an endorsement of those websites The materials at those websites are not part of the materials for this product and use of those websites is at you...

Страница 64: ...periodically check the manufacturer s support websites for updated information and fixes applicable to the system and related software Homologation statement This product may not be certified in your country for connection by any means whatsoever to interfaces of public telecommunications networks Further certification may be required by law prior to making any such connection Contact an IBM repre...

Страница 65: ...ormité à la réglementation d Industrie Canada Cet appareil numérique de la classe A est conforme à la norme NMB 003 du Canada European Community Compliance Statement This product is in conformity with the protection requirements of EU Council Directive 2004 108 EC on the approximation of the laws of the Member States relating to electromagnetic compatibility IBM cannot accept responsibility for an...

Страница 66: ...monics Guideline with Modifications products greater than 20 A per phase Electromagnetic Interference EMI Statement People s Republic of China Declaration This is a Class A product In a domestic environment this product may cause radio interference in which case the user may need to perform practical action Electromagnetic Interference EMI Statement Taiwan The following is a summary of the EMI Tai...

Страница 67: ...Erweiterungskomponenten von Fremdherstellern ohne Empfehlung von IBM gesteckt eingebaut werden EN 55022 Klasse A Geräte müssen mit folgendem Warnhinweis versehen werden Warnung Dieses ist eine Einrichtung der Klasse A Diese Einrichtung kann im Wohnbereich Funk Störungen verursachen in diesem Fall kann vom Betreiber verlangt werden angemessene Maßnahmen zu ergreifen und dafür aufzukommen Deutschlan...

Страница 68: ...otection against harmful interference in a residential installation This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference ...

Страница 69: ...nts of EU Council Directive 2004 108 EC on the approximation of the laws of the Member States relating to electromagnetic compatibility IBM cannot accept responsibility for any failure to satisfy the protection requirements resulting from a non recommended modification of the product including the fitting of non IBM option cards This product has been tested and found to comply with the limits for ...

Страница 70: ... wie in den Handbüchern beschrieben zu installieren und zu betreiben Des Weiteren dürfen auch nur von der IBM empfohlene Kabel angeschlossen werden IBM übernimmt keine Verantwortung für die Einhaltung der Schutzanforderungen wenn das Produkt ohne Zustimmung von IBM verändert bzw wenn Erweiterungskomponenten von Fremdherstellern ohne Empfehlung von IBM gesteckt eingebaut werden Deutschland Einhaltu...

Страница 71: ...ercial Use You may reproduce distribute and display these publications solely within your enterprise provided that all proprietary notices are preserved You may not make derivative works of these publications or reproduce distribute or display these publications or any portion thereof outside your enterprise without the express consent of IBM Rights Except as expressly granted in this permission n...

Страница 72: ...60 Power Systems Racks and rack features ...

Страница 73: ......

Страница 74: ... Printed in USA ...

Отзывы: