4
Power distribution panel top cover
4.
Remove the -48 V dc bus bar shield from the power distribution panel.
Attention:
The bus bar shield must be correctly reinstalled over the -48 V dc return bus bars to
protect against injury while servicing the power distribution panel.
5.
Ensure that the following steps are performed when connecting the dc power source.
a.
At -48 V dc power source, turn off any -48 V dc power sources that will be connected to the
power distribution panel.
b.
After the -48 V dc power sources are turned off, be sure there is a tag or label over the power
source switches or fuses (lock-out/tag-out) to indicate that the power source is turned off
intentionally.
Note:
Ensure that any oxidation on the copper bus bars is removed.
c.
If this is a raised-floor installation and you are working at the back of the rack, route the power
cables up the rack's right side.
d.
Ensure that the external -48 V dc power cable is connected correctly to the -48 V dc bus bar.
e.
Ensure that the external -48 V dc return cable is routed correctly and installed on the return bus
bar.
1
-48 V dc power cable and return power cable
2
Power distribution panel
3
Front of rack
4
-48 V dc power cable and return power cable
Figure 14. Removing the cable channel cover
Figure 15. Routing the power cables
18
Power Systems: Racks and rack features
Содержание 7014-T42