15
4: U
SER
C
ONFIGURABLE
I
TEMS
N
OTE
: S
ETTINGS ARE MADE THROUGH THE SUPPLIED
P
OWER
C
HUTE SOFTWARE OR
THE NETWORK INTERFACE CONNECTION
. R
EFER TO THE SOFTWARE HELP GUIDES FOR DETAILS
.
F
UNCTION
F
ACTORY
D
EFAULT
U
SER
S
ELECTABLE
C
HOICES
D
ESCRIPTION
Automatic Self-Test
Every 14 days
(336 hours)
Every 14 days
(336 hours),
Every 7 days
(168 hours),
On Startup Only,
No Self-Test
This function sets the interval at which the
UPS will execute a self-test.
UPS ID
UPS_IDEN
Up to eight characters
Use this field to uniquely identify the UPS,
(i.e. server name or location) for network
management purposes.
Date of Last Battery
Replacement
Manufacture Date
mm/dd/yy
Reset this date when you replace the inter-
nal battery module.
Minimum Capacity
Before Return from
Shutdown
0 percent
0, 15, 30, 45, 60, 75, 90
percent
The UPS will charge its batteries to the
specified percentage before it powers up
connected equipment, following a low-
battery shutdown.
Voltage Sensitivity
High
High, Medium, Low
The UPS detects and reacts to line voltage
distortions by transferring to battery power
to protect the connected equipment. When
power quality is poor, the UPS may fre-
quently transfer to battery power. If the
connected equipment can operate normally
under such line voltage conditions, reduce
the sensitivity setting to conserve battery’s
capacity and service life.
Alarm Control
Enable
Enable, Mute, Disable
User can mute an ongoing alarm or disable
all existing alarms permanently.
Shutdown Delay
90 seconds
90, 180, 270, 360, 450,
540, 630, 0 seconds
The interval is set between the times when
the UPS receives a shutdown command and
when it shuts off power to the outlets.
Low Battery Warning
2 minutes
2, 5, 8, 11, 14, 17, 20,
23 minutes
PowerChute software provides automatic,
unattended shutdown when the remaining
battery runtime matches this setting while
on battery.
Change the low battery warning interval
default setting to the time that the operating
system or system software requires to
safely shut down.
Synchronized Turn-on
Delay
0 seconds
0, 60, 120, 180, 240,
300, 360, 420 seconds
The UPS will wait the specified time after
the return of utility power before turn-on
(to avoid branch circuit overload).