IBC 30 Скачать руководство пользователя страница 6

INSTALLATION AND OPERATION INSTRUCTIONS

6

IBC INDIRECT WATER HEATERS - ALL MODELS

3.  Zone Valves – The space heating zones use zone valves for each zone, and 

the water heater is controlled with an additional zone valve. Select a valve 

with a low pressure drop, and adequate pipe size to assure minimum flow. 

See Section 8, Mechanical Drawing #4.

B.   Priority or Non-Priority for Hot Water
Option 1 – Priority.

  The demand for space heating is interrupted until the hot 

water demand is satisfied. This option provides the maximum delivery of hot wa-

ter. IBC boilers are easily configured to operate the Hot Water as a priority load.
Priority is recommended when: 
1.  The boiler output is less than 100,000 Btu per hour, or
2.  The boiler output required to satisfy the hot water demand is more than 50% 

of the boiler output needed to satisfy the space heating demand, or

3.  When an interruption in space heating can be tolerated during long domestic 

hot water draws.

The preferred strategy when using an IBC boiler is to use a load circulator for 

domestic hot water and the IBC controller to switch the circulator on and off using 

the IBC control logic and sequential priority hardware. In most cases the delay 

in space heating will not be noticed because of the rapid recovery of the water 

heater. Certain water heater malfunctions, such as a failed sensor or circulator, 

might delay space heating temporarily until the IBC controller internal logic takes 

over and operates all loads equally until the malfunction is corrected.

Option 2 – Non-Priority.

 The boiler output is divided between space heating 

and water heating. Heating of domestic hot water can be reduced during simul-

taneous space and water heating demands. The maximum amount of reduction 

depends on the boiler output, the number of space heating zones calling, the 

space heating target water temperature, and the amount of boiler water flow split 

between the space heating and zones and the water heater zone. Most IBC boil-

ers are now shipped with “Load Pairing” software that can provide DHW priority 

with simultaneous space heating allowed during moderate heating demands.

C.   Locating the water heater.

The water heater should be located in an area where water leakage from the tank 

or connections will not result in damage to areas adjacent to the water heater or 

to lower floors of the structure. When such a location can not be avoided, a suit-

able drain pan must be installed under the water heater, and the drain pan must 

be connected to a drain.
The water heater should be installed as close to the boiler as is practical for easy 

access for service. The unit is designed for installation on combustible flooring 

and in alcoves, closets, etc.

SURFACE

DISTANCE FROM 

COMBUSTIBLES FOR SERVICE

Front

1"

30"

Rear, Right and Left Sides

1"

3"

Top

6”

6”

Bottom

0"

0”

Table 3: Clearances from heater jacket

WARNING

During operation, the T&P 

relief valve may discharge 

large amounts of steam and/

or hot water. Therefore, to 

reduce the potential for bodily 

injury and property damage, 

a discharge line MUST be 

installed that it:

1. is connected from the valve outlet 

with no intervening valve and 

directed downward to a safe point of 

discharge.

2. allows complete drainage of both the 

valve and the discharge line.

3. is independently supported and 

securely anchored so as to avoid 

applied stress on the valve.

4. is as short and straight as possible

5. terminates freely to atmosphere 

where any discharge will be clearly 

visible and is at no risk of freezing.

6. terminates with a plain end which is 

not threaded.

7. is constructed of a material suitable 

for exposure to temperatures of 

375°F or greater.

8. is, over its entire length, of a pipe size 

equal to or greater than that of the 

valve outlet.

DO NOT CAP, PLUG OR OTHERWISE 

OBSTRUCT THE DISCHARGE PIPE 

OUTLET!

CAUTION

To avoid water damage from 

leaks, a drain pan should 

be installed under the water 

heater unless it is installed in 

a location where leaks will not 

cause property damage - see 

Drawing # 6.
If the discharge from a T&P 

relief valve cannot be directed 

into a drain or to an area 

where water damage will not 

occur, a drain pan capable 

of draining away the full, 

continuous discharge flow 

of the relief valve should be 

installed.

Содержание 30

Страница 1: ...IBC 115 HO C FOR SINGLE WATER HEATER INSTALLATIONS For service or repairs to the water heater call your heating contractor Your water heater has been manufactured to provide years of service In order...

Страница 2: ...n hazardous conditions that could result in property damage and injury to occupants which in extreme cases might result in death When using electrical appliances basic safety precautions to reduce the...

Страница 3: ...es for Hot Water Supply Systems ANSI Z21 22 latest edition This valve must be marked with a maximum set pressure not to exceed the marked working pressure of the water heater Install the valve into an...

Страница 4: ...400 14 0 6 6 T P VALVE 1 1 4 NPT BOILER SUPPLY 1 1 4 NPT BOILER RETURN 1 1 2 NPT DOM COLD INLET SENSOR WELL DRAIN C UNITS 8 0 8 0 9 5 3 4 NPT RECIRC PORT 1 1 2 NPT HOT OUTLET T P VALVE BOILER SUPPLY...

Страница 5: ...low through the water heater coil and the pressure drop at minimum flow Calculate the pressure drop across all piping and fittings connected to the water heater zone Be sure to include all zone valves...

Страница 6: ...software that can provide DHW priority with simultaneous space heating allowed during moderate heating demands C Locating the water heater The water heater should be located in an area where water le...

Страница 7: ...supply line to the heater strip back to the tank or nearest mains piping and cap off If oil heating system is to be abandoned completely ensure proper removal and disposal of old oil tank and remainin...

Страница 8: ...g system that is either in place or is to be installed for a new hydronic system installation See Schematic drawings in Section 8 for direction 2 It is recommended that minimum size 1 pipe be used on...

Страница 9: ...tallation Manual for the boiler as well Temperature Sensor The Temperature Sensor supplied with the IBC Water Heater is an NTC Thermistor type with a resistance of 10 000 ohms at 25 C and 3892 IBC doe...

Страница 10: ...HW operation if the DHW Priority setting is higher than the other heating loads Temperature Adjustment The tank sensor controls the maximum water temperature in the water heater If it is set too high...

Страница 11: ...e frequent service Depending on water conditions a varying amount of sediment may collect in the tank Levels requiring service are indicated by a small temperature difference between the boiler supply...

Страница 12: ...to flush all of the cleaning solution from the tank 11 Reinstall the relief valve and the drain piping 12 Open the cold water supply and fill the tank with water Purge the air from the tank and the pi...

Страница 13: ...n Follow steps for Boiler does not operate Check for 24VAC at the zone valve while there is a call for heat if correct voltage is available and connections are good replace the zone valve If the zone...

Страница 14: ...with IBC Water Heater Interlock 1 Interlock 2 Therm 1 Therm 2 Therm 3 Outdoor S Indoor S 2nd Loop S DHW S Boiler Net Ext Cont White Green Black Fuse 5A Fuse 5A Fuse 5A Fuse 5A G1 DHW Pump P2 Fan Coil...

Страница 15: ...20 115 Pumps Only IBC SL 20 115 BOILER IBC DHW Domestic Hot Water Sensor DHW Pump P1 Fan Coil Pump P2 Outdoor Sensor Fan Coil Thermostat Mechanical Drawing 3 FAN COIL NOTE IBC VFC Series boilers have...

Страница 16: ...op S DHW S Boiler Net Ext Cont White Green Black Fuse 5A Fuse 5A Fuse 5A Fuse 5A G1 G2 G3 G4 G5 G6 G7 G8 O1 O2 O3 O4 O5 O6 O7 O8 O9 O10 O11 O12 O13 O14 O15 O16 O17 O18 O19 O20 O21 O22 Auxiliary Interl...

Страница 17: ...iping w DHW Pump and Baseboard system Zone Valves Domestic Hot Water Sensor BB Zone 1 Thermostat Mechanical Drawing 5 BB Zone 1 Valve ZV1 BB Zone 2 Valve ZV2 BB Zone 3 Valve ZV3 Zone Valve end switch...

Страница 18: ...Well Drain Valve and Temperature Pressure Relief Valve An IBC Temperature Sensor is shipped loose with the tank to be inserted into the Temperature Well and wired to the IBC Boiler Control Board on Te...

Страница 19: ...115 F 140 F 115 F 140 F 115 F 140 F 115 F 50 000 139 164 67 92 170 195 67 92 60 000 152 183 80 111 183 214 80 111 80 000 179 219 107 147 210 250 107 147 100 000 205 256 133 184 236 287 133 184 120 000...

Страница 20: ...115 F 140 F 115 F 140 F 115 F 140 F 115 F 50 000 139 164 67 92 170 195 67 92 60 000 152 183 80 111 183 214 80 111 80 000 179 219 107 147 210 250 107 147 100 000 205 256 133 184 236 287 133 184 120 000...

Страница 21: ...21 INSTALLATION AND OPERATION INSTRUCTIONS IBC INDIRECT WATER HEATERS ALL MODELS DATE LICENSED CONTRACTOR DESCRIPTION OF WORK DONE Service Record Notes...

Страница 22: ...ATION AND OPERATION INSTRUCTIONS 22 IBC INDIRECT WATER HEATERS ALL MODELS IBC Technologies Inc 1445 Charles Street Vancouver BC Canada V5L 2S7 Tel 604 877 0277 Fax 604 877 0295 www ibcboiler com 120 1...

Отзывы: