AST0922-940
Page
18
10. Slowly open the water supply valve or return the
bypass valve(s) to the not in bypass" position.
11. Reconnect electric power, and reset the time of
day.
Hydrostatic Test Pressure ……………………………………………………………………………. 300 psi
(2069kPa)
Working Pressure ………………………………………….. 20 to 127 psi (138 to 876 kPa), 100 psi max in
Canada
Voltage ……………………………….. 24V 50 Hz, 24V 60 Hz, 100V 50 Hz, 100V 60 Hz, 230V 50 Hz, 115V 60
Hz
Current ……………………………………………………………………………………………………………….. 50
mA
Operating Temperature …………………………………………………………………..… 34°F (1°C) to 120°F
(49°C)
Humidity ………………………………………………………………...…………….10% to 100%, condensing
allowed
Pressure Tank Thread ………………………………………………………………………………… 2 1/2 in - 8
NPSM
Brine Line Thread ………………………………………………………………………………………... 1/4 in NPT
male
Distributor Tube Diameter Required …………………………………………………………. 13/16 in O.D. (20.6
mm)