SFC 16-125 - Fuel Conversion to Natural Gas (LP to NG) Kit P-807

|

5

Note

:  Allow the unit to operate at High Fire for 3 minutes to stabilize. (The unit operates in manual mode for 10 

minutes then switch back to the normal operating mode. To extend manual mode operation, press the 

Service 

 

and 

Plus

 buttons  together twice while the unit is operating in manual mode to reset the timer for 10 more 

minutes.) Do not make adjustments if the service display shows an “h”.

 5.  Clock the gas meter (see instructions  

Clocking the Meter (for Natural Gas only) on page 6

) to confirm full 

maximum rating plate input. 

 a.  With a combustion analyzer probe in the flue gas test port, check the measured results against 

Table 1 

 - 

High Fire. 

 b.  If the results are outside the permitted range, check the inlet pressure, and confirm that the correct orifice is 

installed. 

 6.  Switch the water heater to low fire by pressing the Service button and Minus button at the same time. The water 

heater will drop to low fire. “L” will show in the service display. 

 a.  Compare the readings with 

Table 1 

- Low Fire. If adjustment is necessary, remove the Low Fire 

Adjustment cap to reveal a Torx head screw. 

 b.  Make tiny adjustments, typically less than 1/8th of a turn at a time. Turn the screw clockwise to increase 

CO

2

 and counter-clockwise to reduce CO

2

. If the target cannot be met, even after a half turn, contact the 

factory. 

 c.  When finished, replace the Low Fire cap, and leave the manual mode by pr AND - 

simultaneously.

 7.  Switch off the unit by pressing the space above the dot. 

 8.  Turn off the gas at the unit's manual gas valve.

 9.  Remove the flue gas analyzer from the test port, and reinstall the test port cap. 

 10.  Remove the gas pressure manometer from the gas valve, and fully close the test port.

 11.  Turn on the gas at the unit’s manual gas valve.

 12.  Ensure there are no gas leaks before reinstalling the front cover. 

 13.  Turn on the unit by pressing the space above the dot.

Completing and Affixing the Conversion Labels

 1.  Fill in the conversion labels (included in the kit) associated with the new fuel type.

 2.  Place the conversion labels onto the unit at the positions indicated on the last page. 

Содержание SFC 16-125

Страница 1: ...codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire an explosion or production of carbon monoxide may result causing pro...

Страница 2: ...the unit to natural gas a combustion CO2 reading must be taken by a qualified technician using properly functioning and calibrated combustion analyzing equipment and the results compared to the values...

Страница 3: ...een 750 900 BTU FT3 To perform a fuel conversion 1 Turn off the gas supply at the manual gas valve 2 Disconnect the electrical power 3 Disconnect the nut at the gas valve outlet top of the gas valve a...

Страница 4: ...s detected After 4 unsuccessful trials for ignition the unit locks out and will need to be manually reset by pressing the Return Arrow button To perform a combustion test and adjustment 1 Turn off the...

Страница 5: ...re L will show in the service display a Compare the readings with Table 1 Low Fire If adjustment is necessary remove the Low Fire Adjustment cap to reveal a Torx head screw b Make tiny adjustments typ...

Страница 6: ...t shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For 2 P...

Страница 7: ...SFC 16 125 Fuel Conversion to Natural Gas LP to NG Kit P 807 7 Where to Place Conversion Labels on the Unit...

Отзывы: