Combustion Test Target Ranges

Figure 1 Gas valve and fan

The Low Fire (zero-offset) valve adjustment cap on the gas valve has been factory set. Do not adjust this screw in the field 

unless indicated  in these instructions. 

After converting the unit to natural gas, a combustion (CO

2

) reading must be taken by a qualified technician using properly 

functioning and calibrated combustion analyzing equipment and the results compared to the values in Table 1.

Natural Gas

CO

2

 Value (%) at High Fire with front cover 

open

CO

2

 Value (%) at Low Fire with front cover 

open

Max. CO

2

 value

10.1%

Actual Value at High Fire 

Min. CO

2

 value

9.1%

9.1%

Table 1 

Combustion test target ranges - CO

2

 / Maximum CO

2

|

Содержание SFC 16-125

Страница 1: ...codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire an explosion or production of carbon monoxide may result causing pro...

Страница 2: ...the unit to natural gas a combustion CO2 reading must be taken by a qualified technician using properly functioning and calibrated combustion analyzing equipment and the results compared to the values...

Страница 3: ...een 750 900 BTU FT3 To perform a fuel conversion 1 Turn off the gas supply at the manual gas valve 2 Disconnect the electrical power 3 Disconnect the nut at the gas valve outlet top of the gas valve a...

Страница 4: ...s detected After 4 unsuccessful trials for ignition the unit locks out and will need to be manually reset by pressing the Return Arrow button To perform a combustion test and adjustment 1 Turn off the...

Страница 5: ...re L will show in the service display a Compare the readings with Table 1 Low Fire If adjustment is necessary remove the Low Fire Adjustment cap to reveal a Torx head screw b Make tiny adjustments typ...

Страница 6: ...t shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For 2 P...

Страница 7: ...SFC 16 125 Fuel Conversion to Natural Gas LP to NG Kit P 807 7 Where to Place Conversion Labels on the Unit...

Отзывы: