SFC 16-125 - Fuel Conversion to Natural Gas (LP to NG) Kit P-807

|

7

Where to Place Conversion Labels on the Unit

 

Содержание SFC 16-125

Страница 1: ...codes and requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire an explosion or production of carbon monoxide may result causing pro...

Страница 2: ...the unit to natural gas a combustion CO2 reading must be taken by a qualified technician using properly functioning and calibrated combustion analyzing equipment and the results compared to the values...

Страница 3: ...een 750 900 BTU FT3 To perform a fuel conversion 1 Turn off the gas supply at the manual gas valve 2 Disconnect the electrical power 3 Disconnect the nut at the gas valve outlet top of the gas valve a...

Страница 4: ...s detected After 4 unsuccessful trials for ignition the unit locks out and will need to be manually reset by pressing the Return Arrow button To perform a combustion test and adjustment 1 Turn off the...

Страница 5: ...re L will show in the service display a Compare the readings with Table 1 Low Fire If adjustment is necessary remove the Low Fire Adjustment cap to reveal a Torx head screw b Make tiny adjustments typ...

Страница 6: ...t shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For 2 P...

Страница 7: ...SFC 16 125 Fuel Conversion to Natural Gas LP to NG Kit P 807 7 Where to Place Conversion Labels on the Unit...