background image

Clocking the Meter (for Natural Gas only)

 1.  Turn off all other appliances and pilots.

 2.  Turn on the boiler and set the boiler to high fire.

 3.  Ensure the boiler has a large load to heat, so that the boiler will not shut off.

 4.  With a Stop-Watch, record the number of seconds for the smallest dial to make 1 full revolution.

 5.  CFH = (3600 x Dial Size) / Seconds

 6.  CFH x 1000 (check local Btu content) = Input Btu’s.

 

Note

For 2 PSI meters multiply CFH x 1.097

For Metric meters multiply CFH x 35.3

For 2 PSI metric meters multiply CFH x 1.097 x 35.3

For Altitude above 4,500' deduct 2% per 1,000’ of altitude from the Input Btu’s.

6

|

Содержание Kit P-805

Страница 1: ...requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire an explosion or production of carbon monoxide may result causing property dama...

Страница 2: ...ns After converting the unit to natural gas a combustion CO2 reading must be taken by a qualified technician using properly functioning and calibrated combustion analyzing equipment and the results co...

Страница 3: ...Chart To perform a fuel conversion 1 Turn off the gas supply at the manual gas valve 2 Disconnect the electrical power 3 Disconnect the nut at the gas valve outlet top of the gas valve and remove the...

Страница 4: ...e is detected After 4 unsuccessful trials for ignition the unit locks out and will need to be manually reset by pressing the Return Arrow button To perform a combustion test and adjustment 1 Turn off...

Страница 5: ...Low Fire If adjustment is necessary remove the Low Fire Adjustment cap to reveal a Torx head screw b Make tiny adjustments typically less than 1 8th of a turn at a time Turn the screw clockwise to inc...

Страница 6: ...l not shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For...

Страница 7: ...SFC 15 99 SFB 15 99 Fuel Conversion to Natural Gas Kit P 805 7 Where to Place Conversion Labels on the Boiler...

Отзывы: