SFC 15-99 / SFB 15-99 - Fuel Conversion to Natural Gas - Kit P-805

|

3

Fuel Conversion Instructions

The following procedure must be carried out by a qualified technician.

Model Number

Orifice Size

SFC 15-99 / SFB 15-99

392

Table 2 

 Natural Gas Orifice Chart

Alternative Natural Gas Orifices - Calorific values 750-

900 BTU/FT

3

Model Number

Orifice Size

SFC 15-99 / SFB 15-99

426

Table 3 

 Natural Gas Orifice Chart

To perform a fuel conversion:

 1.  Turn off the gas supply at the manual gas valve.

 2.  Disconnect the electrical power.

 3.  Disconnect the nut at the gas valve outlet (top of the gas valve), and remove the O-ring and orifice.

 4.  Insert the correct orifice into the O-ring, and re-install into the nut at the gas valve outlet (top of the gas valve), 

and then tighten the nut.

 5.  Restore the gas supply by opening the gas control valve.

 6.  Test for leaks by using an approved leak detection solution on all joints.

 7.  Power on the unit.

Now, carefully follow the procedures on Combustion Testing and Adjustment.

Содержание Kit P-805

Страница 1: ...requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire an explosion or production of carbon monoxide may result causing property dama...

Страница 2: ...ns After converting the unit to natural gas a combustion CO2 reading must be taken by a qualified technician using properly functioning and calibrated combustion analyzing equipment and the results co...

Страница 3: ...Chart To perform a fuel conversion 1 Turn off the gas supply at the manual gas valve 2 Disconnect the electrical power 3 Disconnect the nut at the gas valve outlet top of the gas valve and remove the...

Страница 4: ...e is detected After 4 unsuccessful trials for ignition the unit locks out and will need to be manually reset by pressing the Return Arrow button To perform a combustion test and adjustment 1 Turn off...

Страница 5: ...Low Fire If adjustment is necessary remove the Low Fire Adjustment cap to reveal a Torx head screw b Make tiny adjustments typically less than 1 8th of a turn at a time Turn the screw clockwise to inc...

Страница 6: ...l not shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For...

Страница 7: ...SFC 15 99 SFB 15 99 Fuel Conversion to Natural Gas Kit P 805 7 Where to Place Conversion Labels on the Boiler...