SFC 15-99 / SFB 15-99 - Fuel Conversion to Natural Gas - Kit P-805

|

7

Where to Place Conversion Labels on the Boiler

 

Содержание Kit P-805

Страница 1: ...requirements of the authority having jurisdiction If the information in these instructions is not followed exactly a fire an explosion or production of carbon monoxide may result causing property dama...

Страница 2: ...ns After converting the unit to natural gas a combustion CO2 reading must be taken by a qualified technician using properly functioning and calibrated combustion analyzing equipment and the results co...

Страница 3: ...Chart To perform a fuel conversion 1 Turn off the gas supply at the manual gas valve 2 Disconnect the electrical power 3 Disconnect the nut at the gas valve outlet top of the gas valve and remove the...

Страница 4: ...e is detected After 4 unsuccessful trials for ignition the unit locks out and will need to be manually reset by pressing the Return Arrow button To perform a combustion test and adjustment 1 Turn off...

Страница 5: ...Low Fire If adjustment is necessary remove the Low Fire Adjustment cap to reveal a Torx head screw b Make tiny adjustments typically less than 1 8th of a turn at a time Turn the screw clockwise to inc...

Страница 6: ...l not shut off 4 With a Stop Watch record the number of seconds for the smallest dial to make 1 full revolution 5 CFH 3600 x Dial Size Seconds 6 CFH x 1000 check local Btu content Input Btu s Note For...