3. SCON-CA/CF
A
91
3.5
Setting
Using the teaching tool, set controller parameters. Set the mode toggle switch on the front panel of the
controller to “MANU” side. Refer to the instruction manual for each teaching tool for the applicable version
of the teaching tool that can be applied to EtherNet/IP.
3.5.1
Operation Mode Selecting
Set parameter No. 84 “FMOD: Field bus operation mode.”
[Refer to 3.9 EtherNet/IP Related Parameters.]
Set value
Operation mode
Number of
occupied bytes
0 (Factory setting)
Remote I/O mode
2
1
Position/simplified direct
value mode
8
2
Half direct value mode
16
3
Full direct value mode
32
4
Remote I/O mode 2
12
* Entering any value except for the ones described above will cause an “Excessive Input Value Error”.
3.5.2
Setting the Baud Rate
Set parameter No. 86, “FBRS: Fieldbus baud rate.”
Set value
Baud rate
0 (Factory setting)
Auto negotiation (recommended)
1
10 Mbps, half-duplex
2
10 Mbps, full-duplex
3
100 Mbps, half-duplex
4
100 Mbps, full-duplex
Other than the above
Baud rate setting error
3.5.3
Setting the IP Address
Set parameter No. 140, “IPAD: IP address.”
[Refer to 3.9, “EtherNet/IP Parameters.”]
Settable Range:0.0.0.0 to 255.255.255.255 (It is set to “192.168.0.1” when the machine is delivered from
the factory.)
(Note 1) Exercise caution to avoid IP address duplication.
For details, refer to the operation manuals of the master unit and PLC in which in the master unit
is installed.
(Note 2) When this parameter is set to 0.0.0.0, DHCP (automatic assignment of IP address) is enabled.
Since this setting may result in the IP address being changed unintentionally, it is recommended
that you set the address manually.