N100
plus
Inverter RS485 Interface Instruction Manual
1.2.2
Request frame for setting parameter
Setting 1 parameter and command (note3) of Inverter
(1) External transmit frame
Communication
number
Order
Parameter
Data
CRC Hi
CRC Lo
Clause
Description
Data size
Specifications
Communication
number
Inverter communication
number
1 byte
1~32
Order
Frame type
1 byte
0x06
Parameter
Parameter
2 byte
1st byte : Group
2nd byte : index (Note1)
Data
Data
2 byte
Setting value (Note2)
CRC Hi
-
1 byte
Higher 8bit of 16bit CRC
CRC Lo
-
1 byte
Lower 8bit of 16bit CRC
Table 5 External transmit frame
(2) Inverter response frame
Communication
number
Order
Parameter
Data
CRC Hi
CRC Lo
Clause
Description
Data size
Specifications
Communication
number
Inverter communication
number
1 byte
1~32
Order
Frame type
1 byte
0x06
Parameter
Parameter
2 byte
1st byte : Group
2nd byte : index (Note1)
Data
Data
2 byte
Setting value is response
(note 4)
CRC Hi
-
1 byte
Higher 8bit of 16bit CRC
CRC Lo
-
1 byte
Lower 8bit of 16bit CRC
Table 6 Inverter response frame