N100
plus
Inverter RS485 Interface Instruction Manual
(3) Parameter setting [Note 1]
①
Basic parameter
1st byte : Each group is setting.
Group
1
st
byte
Group
1
st
byte
d
0x01
C
0x05
F
0x02
S
0x06
A
0x03
H
0x07
b
0x04
-
-
Table 7 Basic parameters (1
st
byte)
2
nd
byte : Parameter number setting
Ex) The case of A60 parameter reading or writing
1
st
byte : 0x03
2
nd
byte : 0x3C
②
Trip information
Trip information is 4 parameters. (output frequency, output current, DC link
voltage at trip occurs)
Trip
information
Previous
first trip
Previous
second trip
Previous
third trip
Trip count
1st byte
0x01
0x01
0x01
0x01
0x01
2nd byte
0x0D
0x11
0x15
0x19
0x1D
Table 8 Trip information List (1
st
byte,
2
nd
byte)
③
Trip information items
Trip data
Trip contents
Trip data
Trip contents
1
Over current trip
7
Electric thermal trip
2
Over voltage trip
8
Outside trip
3
Under voltage trip
9
EEROM trouble
4
Arm short trip
10
Communication trouble
5
Reserved
11
USP trip
6
Inverter over heat trip
12
GF trip
Table 9 Trip information items
N100_Inverter RS485 Interface Manual(English).doc
7