Maximum Capacity of Pipe in Cubic Feet of Natural Gas per Hour for Gas Pressures of

0.5 Psig or Less and a Pressure Drop of 0.3 Inch Water Column

(Based on a 0.60 Specific Gravity Gas)

Nominal

Iron Pipe

Size,

Inches

Internal

Diameter,

Inches

Length of Pipe, Feet

10

32
72

132
278
520

1,050
1,600
3,050
4,800
8,500

17,500

20

22
49
92

190
350
730

1,100
2,100
3,300
5,900

12,000

30

18
40
73

152
285
590
890

1,650
2,700
4,700
9,700

40

15
34
63

130
245
500
760

1,450
2,300
4,100
8,300

50

14
30
56

115
215
440
670

1,270
2,000
3,600
7,400

60

12
27
50

105
195
400
600

1,150
1,850
3,250
6,800

70

11
25
46
96

180
370
560

1,500
1,700
3,000
6,200

80

11
23
43
90

170
350
530
990

1,600
2,800
5,800

90

10
22
40
84

160
320
490
930

1,500
2,600
5,400

100

9

21
38
79

150
305
460
870

1,400
2,500
5,100

125

8

18
34
72

130
275
410
780

1,250
2,200
4,500

150

8

17
31
64

120
250
380
710

1,130
2,000
4,100

175

7

15
28
59

110
225
350
650

1,050
1,850
3,800

200

6

14
26
55

100
210
320
610
980

1,700
3,500

1/4"
3/8"
1/2"
3/4"

1"
1-1/4"
1-1/2"
2"
2-1/2"
3"
4"

.326
.493
.622
.824

1.049
1.380
1.610
2.067
2.469
3.026
4.026

Maximum Capacity of Pipe in Thousands of Btu per Hour of Undiluted Liquefied

Petroleum Gases (at 11 Inches Water Column Inlet Pressure)

(Based on a Pressure Drop of 0.5 Inch Water Column)

Nominal

Iron Pipe

Size,

Inches

Length of Pipe, Feet

10

275
567

1071
2205
3307
6221

20

189
393
732

1496
2299
4331

30

152
315
590

1212
1858
3465

40

129
267
504

1039
1559
2992

50

114
237
448
937

1417
2646

60

103
217
409
834

1275
2394

70

96

196
378
771

1180
2205

80

89

185
346
724

1086
2047

90

83

173
322
677

1023
1921

100

78

162
307
630
967

1811

125

69

146
275
567
866

1606

150

63

132
252
511
787

1498

1/2"
3/4"

1"

1-1/4"
1-1/2"
2"

FIGURE 2.7: GAS PIPE SIZING TABLES & EXAMPLE 

Example:

Boiler Model VS-135B is to be installed. The distance from the existing gas meter to the installation site

is 30 ft. What pipe size must be used? The local utility indicates the heating value of natural gas being supplied is
1000 Btu per cu.ft. Determine cubic feet of gas per hour for above boiler model:

135,000 Btu per hour = 135 cu.ft. per hour

1000 Btu per cu.ft.

1. Find 30 ft. in upper portion of the table for natural gas under "Length of Pipe, Feet" heading.
2. Moving down the column, match required capacity. Higher capacity is acceptable. In our case it is 152 cu.ft.
3. Move to left-hand column "Nominal Iron Pipe Size, Inches," to read required pipe size. In our case it is 1/2".

8

TESTING GAS PIPING

For any pressure testing in excess of 1/2 psi, the boiler
and its individual shutoff valve must be isolated from the

piping system by disconnecting them and capping the
outlet(s). For any pressure testing equal to or less than
1/2 psi, the boiler must be isolated from the piping sys-
tem by closing its manual shutoff valve.

Minimum pressure required at the gas valve inlet is 5"
W.C. for natural gas and 11" W.C. for propane. Maxi-
mum pressure allowable at the gas valve inlet is 12"
W.C. If the gas pressure is above these limits, a pres-
sure regulator must be installed. If the gas pressure is

DANGER: Before placing gas piping into service,
carefully test it to assure every joint is gas tight.
Bubble test all joints with a soap solution. NEVER
TEST WITH AN OPEN FLAME AS FIRE OR EXPLO-
SION WILL RESULT.

Содержание VSB2-605

Страница 1: ...mpliance 2 Venting Requirements 2 Chimney Requirements 3 Combustion Air Requirements 3 Water Treatment 3 Shipment of Boiler 3 SECTION 2 BOILER INSTALLATION Step 1 Locating Setting Boiler 4 Step 2 Inst...

Страница 2: ...ms operating under positive pressure When two or more appliances vent into a common flue the area of the common flue should be at least equal to the area of the largest flue plus 50 of the areas of th...

Страница 3: ...e outside or through a vertical duct each opening must have a minimum free area of one square inch per 4000 Btu hr of gas input Horizontal ducts to the outside must have a minimum free area of one squ...

Страница 4: ...ing rain etc during appliance operation and service low water cut off replacement condensate trap control replacement NOTE Do not loosen tie rods on boiler absorption unit They are intended to accommo...

Страница 5: ...g to terminate within 6 of the floor Check local code requirements if in doubt Discharge piping must be of same size or larger than the relief valve outlet and should be run as short and straight as p...

Страница 6: ...must be accessible for servicing and checking position indicator Remove hairpin shipping clip which holds damper blade in closed position and observe that damper blade rotates slowly to open position...

Страница 7: ...w for servicing Check local codes and utilities for any special requirements and procedures Pipe joint compound pipe dope must be compatible with the fuel natural gas or propane being used FIGURE 2 6...

Страница 8: ...1180 2205 80 89 185 346 724 1086 2047 90 83 173 322 677 1023 1921 100 78 162 307 630 967 1811 125 69 146 275 567 866 1606 150 63 132 252 511 787 1498 1 2 3 4 1 1 1 4 1 1 2 2 FIGURE 2 7 GAS PIPE SIZIN...

Страница 9: ...nsulation may melt or degrade expos ing bare wire NOTE Boiler transformer must not be used to power external accessories i e zone valves relays etc Otherwise transformer will be overload ed and burn o...

Страница 10: ...ENS 7 PILOT IS IGNITED AND SENSOR SENSES FLAME 9 UNIT OPERATES UNTIL THERMOSTAT OR OPERATING CONTROL IS SATISFIED FIELD WIRING FACTORY WIRING LOW WATER CUTOFF ARE ENERGIZED CONTROL SWITCH SPILL BLUE B...

Страница 11: ...ION 1 Check combination gas valve on boiler and make sure it is in the OFF position 2 For vent damper equipped models with the thermo stat set to call for heat observe that vent damper posi tion indic...

Страница 12: ...ng vary more than 3 from factory set pressures If rated input cannot be obtained with adjustment gas supply pressure or orifice size may be cause Consult local utility and Hydrotherm 8 Gas burner orif...

Страница 13: ...electric power to the appliance 4 Remove control access panel if applicable 5 Rotate gas control knob clockwise to OFF 6 Wait five 5 minutes to clear out any gas Then smell for gas including near the...

Страница 14: ...ith an ignition device which automatically lights the pilot Do not try to light the pilot by hand 5 Remove control access panel if applicable 6 Rotate gas control knob clockwise to OFF 7 Wait five 5 m...

Страница 15: ...t off has been utilized follow the manufacturer s maintenance instructions As a minimum Inspect the probe and test the operation of electronic con trols at least once a year Remove clean and inspect t...

Страница 16: ...ifices 3 Check orifices for proper drill size Size is stamped onto the body of the brass orifice see Figure 4 1 Size can also be checked by using a pin gauge 4 All orifices are screwed into the manifo...

Страница 17: ...P BBR10 62 3327 1 1 1 1 15 Manifold 24 1411 1 Manifold 24 1413 1 1 Manifold 24 1414 1 16 Gas Valve 24 V Nat Gas 02 1543 1 1 1 1 VR8204 H 1006 Gas Valve 24 V L P Gas 02 1546 1 1 1 1 VR8204 H 1014 17 B...

Страница 18: ...1026 1 1 1 1 38 Pressuretrol 02 4807 1 1 1 1 39 Tee 1 2 X 1 2 X 1 4 56 1351 1 1 1 1 40 Press Gauge 20 3002 1 1 1 1 41 Water Gauge 20 2005 1 1 1 1 42 Nipple 3 4 X 14 53 1136 1 1 1 1 43 Coupling 3 4 56...

Страница 19: ...78 1 1 1 1 73 Nipple 1 2 X 3 Brass 53 1111 2 2 2 2 74 Nipple 1 2 X Close 53 1076 1 1 1 1 75 Nipple 1 2 X 3 53 1080 2 2 2 2 PARTS FOR VS B JACKET ASSEMBLY SEE FIGURE 3 Jacket Complete BM 2648 1 Jacket...

Страница 20: ...2 3327 1 1 1 1 19 Thermocouple Q309A 04 1302 1 1 1 Thermocouple Q309A 3 FT 04 1306 1 20 Pilot Line w Fittings BM 8078 1 1 1 Pilot Line w Fitting BM 8079 1 22 Gas Valve NG VR8200H1129 02 1540 1 1 1 1 G...

Страница 21: ...21 FIGURE 1 VS B GENERAL ASSEMBLY 45 43 26 21 20 19 24 33 29 44 15 14 6 12 10 7 17 13 5 42 30 22 16 11 8 9 27 28 23 31 27 28 25 4 1 3 2 18 65 66 32 41 39 35 36 37 38 40 34 46 77...

Страница 22: ...N FIGURE 1 69 HONEYWELL RW700A LOW WATER CUT OFF AND FITTINGS McDONNELL MILLER 47 2 LOW WATER CUT OFF FEEDER AND FITTINGS 60 63 61 59 62 58 SAME AS IN FIGURE 1 FIGURE 2 LOW WATER CUT OFF AND FITTINGS...

Страница 23: ...23 NOTES...

Страница 24: ...260 NORTH ELM ST WESTFIELD MA 01085 413 564 5515 FAX 413 568 9613 5211 CREEKBANK ROAD MISSISSAUGA ONTARIO L4W 1R3 905 625 2991 FAX 905 625 6610...

Отзывы: