HydroTherm KN SERIES Скачать руководство пользователя страница 8

8

P/N 42-9452 8/08 Copyright Hydrotherm

KN USER’S CONTROL MANUAL

Figure 6

 

Indoor Air Reset wiring to IAR terminals with 
4-wire zone valves and no zone controller 

(see Figure 7, page 9 for terminal block 

6

 location)

Method 1:  HeatNet modulation – local control 

(cont.)

1

IAR (Indoor Air Reset) wiring, when used

Heat Demand terminal connections — Th e end switch leads from the zone valves 
must connect to the Heat Demand terminals on the electrical connection board as 
shown in Figure 7, page 9.

See Figure 6 for typical wiring to the IAR inputs when using 4-wire zone valves 
without a zone controller. For other applications, such as circulator relays or zone 
controllers, see Appendix A in the Boiler manual..

 

Polarity

 — Th e connections to the 

IAR

 positive terminals (

IAR +

must be to the same location on the zone valve as the thermostat wire, 
as shown in Figure A1. Th e connections to the 

IAR

 negative terminals 

(

IAR –

) must be from the zone valve terminal connected to the 24VAC 

common line, as shown. Connecting the wires incorrectly can cause the 
transformer to be shorted out and damaged. Verify the wiring with a 
voltmeter.

  Always use a voltmeter to check the leads coming from the end switches 

of the zone valves. With the thermostat calling for heat, connect the 
voltmeter leads across the wires coming from the end switches. If 
the meter shows a voltage reading, the zone valve wires are incorrect. 
Change the wiring and retest. DO NOT connect the wires to the boiler 
until you have tested as described. Incorrect wiring can damage the 
boiler control or other system components.

If there is only one transformer feeding all of the zone valves in the system, you can 
omit the wires to the 

IAR

 negative terminals (

IAR –

) on all but one of the zone 

valves. Th is is because these terminals are jumpered internally on the electrical 
connection board. If there is more than one transformer, provide one wire from 
each transformer common side to one of the 

IAR

 negative terminals (

IAR –

).

Sensor wiring

Header sensor is required

 — A header sensor must be installed in the system 

supply piping. 

Connect the header sensor ONLY to the master boiler

. Install 

the header sensor in an immersion well. Locate the sensor where it will accurately 
sense the system water supply temperature. Connect the sensor leads to the electri-
cal connection board as shown in Figure 8, page 10.

Outdoor reset application

 — To operate with outdoor reset, purchase and in-

stall an outdoor sensor. Mount the sensor such that it is shielded from direct sun-
light if possible and not likely to be covered by snow drift s or debris. Connect the 
outdoor sensor leads to the master boiler’s electrical connection board as shown 
in Figure 8, page 10. (Member boilers could have their own outdoor sensor if they 
will be operated in override mode by closing the Heat Demand terminals.)

Return water temperature sensor

 — Th e return water temperature sensor 

is optional, only needed if you want to automatically control the boiler postpurge 
pump cycle time. Install the sensor in a well in the boiler return piping. Connect 
the sensor leads to the electrical connection board as shown in Figure 8, page 10. 

DHW wiring

To operate the boiler for domestic water heating with a storage tank, install and pipe 
the tank according to the tank manufacturer’s instructions and the recommended 
piping diagrams in this manual. Consult the factory for applications not covered.

Th e circulator used for DHW must be operated by a circulator relay or zone con-
troller that is activated when the tank aquastat calls for heat.

Connect the tank aquastat terminals across the DHW DEMAND terminals on the 
master boiler’s electrical connection board as shown in Figure 7, page 9. (Member 
boilers could be connected to tank aquastats if they are piped appropriately and 
intended to operate in override mode.)

Содержание KN SERIES

Страница 1: ...pply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guidelines to clean repair or repla...

Страница 2: ...l controller ThecontrolmethodusedbytheHeatNetcontrolisbasedondigitalcommunications whicheliminatesthe needforanalogcontrolsignals Analogsignalinputsaresupported butahigherlevelofcontrolprecision repea...

Страница 3: ...ter cutoff if desired To flow switch when used Used to activate combustion air damper if desired To combustion air damper proving switch required when controlling combustion air damper Indoor air rese...

Страница 4: ...4 P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL The KN boiler with HeatNetTM control...

Страница 5: ...e RS485 interface board and cable above Boiler setup is essentially the same as for method 1 with the exception that each boiler must be assigned both a HeatNet network address and an address for the...

Страница 6: ...service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 10 1 1 2 3 Figure 1 Electrical connection board see item 10 page 3 for location Also see the wiring sum...

Страница 7: ...at pocket ing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See the Boiler manual f...

Страница 8: ...board If there is more than one transformer provide one wire from each transformer common side to one of the IAR negative terminals IAR Sensor wiring Header sensor is required A header sensor must be...

Страница 9: ...P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL Figure 7 KN wiring summary wiring to electrical connection board Method 1 HeatNet modulation local control cont 1 Also see Figure 2 page...

Страница 10: ...erm KN USER S CONTROL MANUAL KN 2 only Figure 8 KN wiring summary wiring to electrical connection board continued see Figure 7 page 9 for terminal strip locations Also see Figure 5 page 7 Method 1 Hea...

Страница 11: ...temperature if member boilers were to input heat to the system without control from the master DHW operation in particular would raise the supply temperature from overriding boilers to the DHW Setpoi...

Страница 12: ...he parameter explanations in Table 8 page 25 through page 29 When adjusting the limit band operating limit OP LIMIT local setpoint LOC SETPOINT and DHW setpoint make sure the operating temperature ban...

Страница 13: ...15 F If the display shows a blank space such as 123_56789ABC the control does not detectthemissingboiler boiler4 ChecktheyellowLEDonthecommunication port of the missing boiler NORMAL connection LED s...

Страница 14: ...lve 31 Present Boiler Detected Overview This method uses an RS485 digital communications cable withtheModbusprotocoltocontrolaboilerorHeatNetnet work TheboilerorboilernetworkwilloperateasintheHeatNetl...

Страница 15: ...has been running For instance Register 29 65536 Register 30 Boiler 1 runtime in seconds Boiler 1 is the master boiler Boilers 2 16 are member boilers 0 4294967295 seconds BACnet or LonWorks protocols...

Страница 16: ...ig ure 12 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 1 1 2 3 Figure 11 Electrical connection board see item 10 page 3 for location...

Страница 17: ...pocketing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See the Boiler manual for c...

Страница 18: ...return water temperature sensor DHW wiring ONLY if using DHW override mode The boiler or boilers must be piped with isolation valves and wired for override operation Override of the 4 20mA input will...

Страница 19: ...19 P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL Method 3 External 4 20ma control continued 3 Figure 16 KN wiring summary wiring to electrical connection board...

Страница 20: ...yright Hydrotherm KN USER S CONTROL MANUAL Method 3 External 4 20ma control continued 3 KN 2 only Figure 17 KN wiring summary wiring to electrical connection board continued see Figure 7 page 9 for te...

Страница 21: ...revent the boiler for attempting to cycle during the setup process See Control menus and adjustments beginning on page 22 for a complete list of control parameters and explanations Carefully read the...

Страница 22: ...wn providing information on various setpoints and parameters The display LOC SET means the setpoint temperature Figure 18 shows the fac tory default values Accessing setup menus With the display in ST...

Страница 23: ...ARVALUES Display only not changeable here shows values for 8 zones 70 70 70 70 70 70 70 70 OUTDOOR AIR OA SHUTDOWN OFF ON or OFF OA SHUTDOWN OFF OA SETPT 68 F 40 to 100 F OA SETPT 68 F OA RESET OFF ON...

Страница 24: ...minutes 10 MINUTES 0 SECONDS SHED BOILER DLY 2 minutes 0 to 15 minutes 2 MINUTES 0 SECONDS MOD DELAYTIME 10 seconds 0 to 60 minutes 0 MINUTES 10 SECONDS MOD MAX LAST 50 25 to 100 STOP MOD MAX 50 STOP...

Страница 25: ...HW Demand terminals see a closed contact DHW tank temperature control calls for heat for example OP LIMIT SETPOINTS This is the temperature at the boiler outlet or header sensor that will cause the co...

Страница 26: ...e High water at low outside air means the design water temperature for maximum load at ODT or outside design temperature for the installation The other end of the reset curve is the low water temperat...

Страница 27: ...PROTECTION AUX FUNCTIONS Select YES to have the control alarm and disable the DHW demand input if a DHW demand lasts for more than 60 minutes SYSTEM CLOCK Set the system clock time day of week month...

Страница 28: ...left at factory default D ERIVAT ADVANCED SETUP MODULATION PID This parameter should generally be left at factory default BAND ADVANCED SETUP MODULATION PID This parameter should generally be left at...

Страница 29: ...omputer The program will start and show an option screen Select Install USB Drivers to install the program onto the computer After the USB driver installation is complete select Install Firmware Updat...

Страница 30: ...ough the log entries entry number and date are on the first line of the log screen Each log entry includes three screens as described below The top line remains the same in all three and contains the...

Страница 31: ...ected to it If all grounding is correct there may be an issue with radiated or induced electrical noise interference Thismaybecausedbyarcingacrossacontactor scontactswhenstartingapumpmotororalargeelec...

Страница 32: ...up the header sensor is auto detected If the temperature of the header sensor at power up is greater than 25 F and less than 240 F it is considered a valid sensor The boiler will default to the MEMBER...

Отзывы: