P/N 42-9452 8/08 Copyright Hydrotherm

KN USER’S CONTROL MANUAL

Figure 10

 

RS485 communications board

Turn on power to the master boiler and set its on/off  switch to ON.
You should hear at least 2 beeps.
Th e control’s fi rmware version number will display.

 Aft er the control’s timer fi nishes, the display will 

 

show STANDBY and SYS SET. Th

 is verifi es that 

 

the master boiler is setup correctly as the master. 

Th e same display will show on member boilers when there is a call for heat from 
the master boiler. When there is no call for heat at a member boiler, the display will 
show LOC SET instead.
If the master is functioning correctly, the yellow LED’s on the H-Link jack ports 
will blink. Th e blinking indicates that the master is trying to communicate with 
member boilers.
If a FAULT message is displayed, clear the faults until the STANDBY message is 
displayed. Refer to troubleshooting suggestions at the end of this manual if you 
cannot resolve the issue.

Member boiler cables

Begin with the fi rst member boiler.
Plug the other end of the master boiler’s communications cable to the member boiler’s 
input port (Figure 10, page 13, item 2 for RJ45 cable or item 4 for 3-wire cable).
Connect cables to all of the member boilers by cabling from one to the next. Connect 
incoming cables to item 1 or 4, Figure 10, page 13. Connect outgoing cables to item 
2 or 4. (Note that shielded cable wires will share terminals when using item 4.)

Check the network

Turn the power on and the on/off  switch to ON for all of the member boilers.
Allow time for each boiler to initialize.
Aft er about 30 seconds, the master boiler should recognize the member boilers.

 Navigate to the BOILERS menu, then to HEAT 

 

NET BOILERS display. Th e master control will 

 

show the boilers it recognizes. Values from 10 to 

15 will display as lett ers (10=A, 11=B, 12=C, 13=D, 14=E and 15=F).
If the display shows a blank space, such as “123_56789ABC,” the control does not 
detect the missing boiler (boiler 4). Check the yellow LED on the communication 
port of the missing boiler.
NORMAL connection — LED should fl ash steadily, about twice per second.
TERMINATION incorrect — LED will fl ash rapidly and stay on.
OPEN connection — LED does not fl ash at all.
If a FAULT message is displayed, clear the faults until the STANDBY message is 
displayed. Refer to troubleshooting suggestions at the end of this manual if you 
cannot resolve the issue.

Start the system

Turn off  power to all boilers.
Connect all call for heat wiring to the boilers.
Turn on power to all boilers and turn the on/off  switches to ON.
Th e boilers should now operate normally, as described in the Boiler manual.
Th e master boiler will sequence and modulate boilers as necessary to control the 
water temperature.
Th e master boiler will show the number of boilers fi ring as well as the temperature 
and heat band display. Use the UP/DOWN keys to scroll through the displays to 
watch the process of starting and stopping boilers.

2.
3.
4.
5.

6.

7.

1.
2.

3.

1.
2.
3.
4.

5.

6.
7.
8.
9.

1.
2.
3.
4.
5.

6.

RJ45 HeatNet cable IN from master or previous 
member
RJ45 HeatNet cable OUT to next member boiler
Shielded wire (3-2ire), option to RJ45 cable, Heat-
Net communications INPUT and connection for 
additional boilers on the network
Shielded wire (option to RJ45 cable) Modbus INPUT 
from building management system
USB cable port (for USB cable connection to a PC — 
required when updating control fi rmware)
RJ45 cable from building management system, when 
used
Plug for insertion into KN control electrical connec-
tion panel (see page 3)
NOT SHOWN — An optional plug-in bridge is re-
quired to interface with building management systems 
that use BACnet or LonWorks protocol. Th e KN 
control supports Modbus protocol with no additional 
components except the RS485 interface board.

1.

2.
3.

4.

5.

6.

7.

8.

Method 1:  HeatNet modulation – local control 

(cont.)

1

Содержание KN SERIES

Страница 1: ...pply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guidelines to clean repair or repla...

Страница 2: ...l controller ThecontrolmethodusedbytheHeatNetcontrolisbasedondigitalcommunications whicheliminatesthe needforanalogcontrolsignals Analogsignalinputsaresupported butahigherlevelofcontrolprecision repea...

Страница 3: ...ter cutoff if desired To flow switch when used Used to activate combustion air damper if desired To combustion air damper proving switch required when controlling combustion air damper Indoor air rese...

Страница 4: ...4 P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL The KN boiler with HeatNetTM control...

Страница 5: ...e RS485 interface board and cable above Boiler setup is essentially the same as for method 1 with the exception that each boiler must be assigned both a HeatNet network address and an address for the...

Страница 6: ...service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 10 1 1 2 3 Figure 1 Electrical connection board see item 10 page 3 for location Also see the wiring sum...

Страница 7: ...at pocket ing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See the Boiler manual f...

Страница 8: ...board If there is more than one transformer provide one wire from each transformer common side to one of the IAR negative terminals IAR Sensor wiring Header sensor is required A header sensor must be...

Страница 9: ...P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL Figure 7 KN wiring summary wiring to electrical connection board Method 1 HeatNet modulation local control cont 1 Also see Figure 2 page...

Страница 10: ...erm KN USER S CONTROL MANUAL KN 2 only Figure 8 KN wiring summary wiring to electrical connection board continued see Figure 7 page 9 for terminal strip locations Also see Figure 5 page 7 Method 1 Hea...

Страница 11: ...temperature if member boilers were to input heat to the system without control from the master DHW operation in particular would raise the supply temperature from overriding boilers to the DHW Setpoi...

Страница 12: ...he parameter explanations in Table 8 page 25 through page 29 When adjusting the limit band operating limit OP LIMIT local setpoint LOC SETPOINT and DHW setpoint make sure the operating temperature ban...

Страница 13: ...15 F If the display shows a blank space such as 123_56789ABC the control does not detectthemissingboiler boiler4 ChecktheyellowLEDonthecommunication port of the missing boiler NORMAL connection LED s...

Страница 14: ...lve 31 Present Boiler Detected Overview This method uses an RS485 digital communications cable withtheModbusprotocoltocontrolaboilerorHeatNetnet work TheboilerorboilernetworkwilloperateasintheHeatNetl...

Страница 15: ...has been running For instance Register 29 65536 Register 30 Boiler 1 runtime in seconds Boiler 1 is the master boiler Boilers 2 16 are member boilers 0 4294967295 seconds BACnet or LonWorks protocols...

Страница 16: ...ig ure 12 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 1 1 2 3 Figure 11 Electrical connection board see item 10 page 3 for location...

Страница 17: ...pocketing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See the Boiler manual for c...

Страница 18: ...return water temperature sensor DHW wiring ONLY if using DHW override mode The boiler or boilers must be piped with isolation valves and wired for override operation Override of the 4 20mA input will...

Страница 19: ...19 P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL Method 3 External 4 20ma control continued 3 Figure 16 KN wiring summary wiring to electrical connection board...

Страница 20: ...yright Hydrotherm KN USER S CONTROL MANUAL Method 3 External 4 20ma control continued 3 KN 2 only Figure 17 KN wiring summary wiring to electrical connection board continued see Figure 7 page 9 for te...

Страница 21: ...revent the boiler for attempting to cycle during the setup process See Control menus and adjustments beginning on page 22 for a complete list of control parameters and explanations Carefully read the...

Страница 22: ...wn providing information on various setpoints and parameters The display LOC SET means the setpoint temperature Figure 18 shows the fac tory default values Accessing setup menus With the display in ST...

Страница 23: ...ARVALUES Display only not changeable here shows values for 8 zones 70 70 70 70 70 70 70 70 OUTDOOR AIR OA SHUTDOWN OFF ON or OFF OA SHUTDOWN OFF OA SETPT 68 F 40 to 100 F OA SETPT 68 F OA RESET OFF ON...

Страница 24: ...minutes 10 MINUTES 0 SECONDS SHED BOILER DLY 2 minutes 0 to 15 minutes 2 MINUTES 0 SECONDS MOD DELAYTIME 10 seconds 0 to 60 minutes 0 MINUTES 10 SECONDS MOD MAX LAST 50 25 to 100 STOP MOD MAX 50 STOP...

Страница 25: ...HW Demand terminals see a closed contact DHW tank temperature control calls for heat for example OP LIMIT SETPOINTS This is the temperature at the boiler outlet or header sensor that will cause the co...

Страница 26: ...e High water at low outside air means the design water temperature for maximum load at ODT or outside design temperature for the installation The other end of the reset curve is the low water temperat...

Страница 27: ...PROTECTION AUX FUNCTIONS Select YES to have the control alarm and disable the DHW demand input if a DHW demand lasts for more than 60 minutes SYSTEM CLOCK Set the system clock time day of week month...

Страница 28: ...left at factory default D ERIVAT ADVANCED SETUP MODULATION PID This parameter should generally be left at factory default BAND ADVANCED SETUP MODULATION PID This parameter should generally be left at...

Страница 29: ...omputer The program will start and show an option screen Select Install USB Drivers to install the program onto the computer After the USB driver installation is complete select Install Firmware Updat...

Страница 30: ...ough the log entries entry number and date are on the first line of the log screen Each log entry includes three screens as described below The top line remains the same in all three and contains the...

Страница 31: ...ected to it If all grounding is correct there may be an issue with radiated or induced electrical noise interference Thismaybecausedbyarcingacrossacontactor scontactswhenstartingapumpmotororalargeelec...

Страница 32: ...up the header sensor is auto detected If the temperature of the header sensor at power up is greater than 25 F and less than 240 F it is considered a valid sensor The boiler will default to the MEMBER...