KN USER’S CONTROL MANUAL

Control menus and adjustments 

(continued)

4

Menu item

Under . . .

Explanation

HEAT BAND

BOILERS

The heat band is the height of the modulating 
band. When the water temperature is between ½ 
the heat band above or below the setpoint 
temperature, boiler fi ring rate modulates. Boilers 
are at minimum input at the upper end of the band 
and maximum input at the lower end of the band. 
Boilers come on only if the water temperature is 
below the band. Boilers stage off  when the water 
temperature is above the band.

LOC SETPT

SETPOINTS

Setpoint temperature controlled by the KN control.

NOTE: If the control is operated by a Master control or by a remote control (building management 
system, 4-20ma control, etc.), this setpoint temperature only comes into play when the KN-2 
control is in override mode (such as by closing its Heat Demand or DHW Demand terminals).

SOURCE

SETPOINTS

Specifi es where the space heating setpoint temperature comes from:

AUTO means the KN control determines the setpoint (using local setpoint, outdoor reset or 
header temperature setpoint).

The option is “4-20ma.” If 4-20 ma is selected, the KN control determines setpoint based on the 
signal it receives at the 4-20ma terminals on the connection board. The setpoint temperature 
(°F) equals the signal current (ma) divided by 0.09; example, a signal of 10ma will cause a 
setpoint of 10/0.09 = 110°F.

DHW SETPT

SETPOINTS

This is the setpoint temperature for the boiler outlet water (or header water temperature) when 
the DHW Demand terminals see a closed contact (DHW tank temperature control calls for heat, 
for example).

OP LIMIT

SETPOINTS

This is the temperature at the boiler outlet (or header sensor) that will cause the control to shut 
down on high temperature limit. It must be high enough above the upper end of the heat band 
to avoid nuisance cycling.

The maximum setting is 205°F.

Example: If the boiler setpoint is 180°F, and the heat band is 30°F, the upper end of the heat 
band is 180  + 30/2 = 195°F. The limit band (see below) must be set at 10°F so the OP LIMIT 
setting can be: 195 + 10 = 205°F (maximum allowable setting).

The operating limit setting (OP LIMIT) always limits boiler outlet water temperature, regardless 
of how the boiler is controlled (HeatNet member, 4-20ma control or stand-alone). The limit 
band (see below) determines when the boiler begins to be forced to reduce input as the outlet 
temperature rises toward the limit setting.

LIMIT BAND

SETPOINTS

If the boiler outlet water temperature rises toward 
the limit setting (OP LIMIT, above), the KN control 
will begin to reduce the boiler’s fi ring rate when 
the temperature gets within the LIMIT BAND 
degrees F below the operating limit setting. At 
the lower end of the limit band, the boiler can fi re 
up to maximum input (100%). By the time the 
temperature reaches the upper end of the band 
(the OP LIMIT setting), the boiler is limited to 
minimum input (20%).

The limit band reduces the likelihood of short cycling on boilers controlled by a master control 
or a remote control by reducing boiler maximum allowable fi ring rate as the temperature rises 
toward the limit setting. Make sure the lower end of the limit band is above the upper end of the 
heat band.

Table 8

 

Setup menus — parameter explanations

Содержание KN SERIES

Страница 1: ...pply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guidelines to clean repair or repla...

Страница 2: ...l controller ThecontrolmethodusedbytheHeatNetcontrolisbasedondigitalcommunications whicheliminatesthe needforanalogcontrolsignals Analogsignalinputsaresupported butahigherlevelofcontrolprecision repea...

Страница 3: ...ter cutoff if desired To flow switch when used Used to activate combustion air damper if desired To combustion air damper proving switch required when controlling combustion air damper Indoor air rese...

Страница 4: ...4 P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL The KN boiler with HeatNetTM control...

Страница 5: ...e RS485 interface board and cable above Boiler setup is essentially the same as for method 1 with the exception that each boiler must be assigned both a HeatNet network address and an address for the...

Страница 6: ...service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 10 1 1 2 3 Figure 1 Electrical connection board see item 10 page 3 for location Also see the wiring sum...

Страница 7: ...at pocket ing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See the Boiler manual f...

Страница 8: ...board If there is more than one transformer provide one wire from each transformer common side to one of the IAR negative terminals IAR Sensor wiring Header sensor is required A header sensor must be...

Страница 9: ...P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL Figure 7 KN wiring summary wiring to electrical connection board Method 1 HeatNet modulation local control cont 1 Also see Figure 2 page...

Страница 10: ...erm KN USER S CONTROL MANUAL KN 2 only Figure 8 KN wiring summary wiring to electrical connection board continued see Figure 7 page 9 for terminal strip locations Also see Figure 5 page 7 Method 1 Hea...

Страница 11: ...temperature if member boilers were to input heat to the system without control from the master DHW operation in particular would raise the supply temperature from overriding boilers to the DHW Setpoi...

Страница 12: ...he parameter explanations in Table 8 page 25 through page 29 When adjusting the limit band operating limit OP LIMIT local setpoint LOC SETPOINT and DHW setpoint make sure the operating temperature ban...

Страница 13: ...15 F If the display shows a blank space such as 123_56789ABC the control does not detectthemissingboiler boiler4 ChecktheyellowLEDonthecommunication port of the missing boiler NORMAL connection LED s...

Страница 14: ...lve 31 Present Boiler Detected Overview This method uses an RS485 digital communications cable withtheModbusprotocoltocontrolaboilerorHeatNetnet work TheboilerorboilernetworkwilloperateasintheHeatNetl...

Страница 15: ...has been running For instance Register 29 65536 Register 30 Boiler 1 runtime in seconds Boiler 1 is the master boiler Boilers 2 16 are member boilers 0 4294967295 seconds BACnet or LonWorks protocols...

Страница 16: ...ig ure 12 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 1 1 2 3 Figure 11 Electrical connection board see item 10 page 3 for location...

Страница 17: ...pocketing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See the Boiler manual for c...

Страница 18: ...return water temperature sensor DHW wiring ONLY if using DHW override mode The boiler or boilers must be piped with isolation valves and wired for override operation Override of the 4 20mA input will...

Страница 19: ...19 P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL Method 3 External 4 20ma control continued 3 Figure 16 KN wiring summary wiring to electrical connection board...

Страница 20: ...yright Hydrotherm KN USER S CONTROL MANUAL Method 3 External 4 20ma control continued 3 KN 2 only Figure 17 KN wiring summary wiring to electrical connection board continued see Figure 7 page 9 for te...

Страница 21: ...revent the boiler for attempting to cycle during the setup process See Control menus and adjustments beginning on page 22 for a complete list of control parameters and explanations Carefully read the...

Страница 22: ...wn providing information on various setpoints and parameters The display LOC SET means the setpoint temperature Figure 18 shows the fac tory default values Accessing setup menus With the display in ST...

Страница 23: ...ARVALUES Display only not changeable here shows values for 8 zones 70 70 70 70 70 70 70 70 OUTDOOR AIR OA SHUTDOWN OFF ON or OFF OA SHUTDOWN OFF OA SETPT 68 F 40 to 100 F OA SETPT 68 F OA RESET OFF ON...

Страница 24: ...minutes 10 MINUTES 0 SECONDS SHED BOILER DLY 2 minutes 0 to 15 minutes 2 MINUTES 0 SECONDS MOD DELAYTIME 10 seconds 0 to 60 minutes 0 MINUTES 10 SECONDS MOD MAX LAST 50 25 to 100 STOP MOD MAX 50 STOP...

Страница 25: ...HW Demand terminals see a closed contact DHW tank temperature control calls for heat for example OP LIMIT SETPOINTS This is the temperature at the boiler outlet or header sensor that will cause the co...

Страница 26: ...e High water at low outside air means the design water temperature for maximum load at ODT or outside design temperature for the installation The other end of the reset curve is the low water temperat...

Страница 27: ...PROTECTION AUX FUNCTIONS Select YES to have the control alarm and disable the DHW demand input if a DHW demand lasts for more than 60 minutes SYSTEM CLOCK Set the system clock time day of week month...

Страница 28: ...left at factory default D ERIVAT ADVANCED SETUP MODULATION PID This parameter should generally be left at factory default BAND ADVANCED SETUP MODULATION PID This parameter should generally be left at...

Страница 29: ...omputer The program will start and show an option screen Select Install USB Drivers to install the program onto the computer After the USB driver installation is complete select Install Firmware Updat...

Страница 30: ...ough the log entries entry number and date are on the first line of the log screen Each log entry includes three screens as described below The top line remains the same in all three and contains the...

Страница 31: ...ected to it If all grounding is correct there may be an issue with radiated or induced electrical noise interference Thismaybecausedbyarcingacrossacontactor scontactswhenstartingapumpmotororalargeelec...

Страница 32: ...up the header sensor is auto detected If the temperature of the header sensor at power up is greater than 25 F and less than 240 F it is considered a valid sensor The boiler will default to the MEMBER...

Отзывы: