background image

2

P/N 42-9452 8/08 Copyright Hydrotherm

KN USER’S CONTROL MANUAL

The KN boiler — HeatNet

TM

 control

Control overview

Th e KN HeatNet control monitors boiler temperature and limit circuit inputs, modulating boiler fi ring 
rate to meet demand. Th e control uses microprocessor electronics, watching time-average response from 
the system to anticipate how much heat the system needs. Coupled with the fi ve-to-one turndown of the 
KN boiler, this results in maximum possible condensing-mode operation. Th e KN boiler will provide 
unmatched seasonal effi  ciency.

Indoor air reset (IAR)

HydroTh erm’s unique approach to boiler output regulation is its Indoor Air Reset function. Th e control 
monitors the demand from up to 8 diff erent zones. Watching the demand duration and response to supply 
temperature, averaging over time, the HeatNet control anticipates system needs. It sets boiler maximum 
fi ring rate and adjusts supply water temperature to fi ne-tune boiler heat output. All that is required to 
enable IAR is to connect thermostat circuit wires to the IAR inputs. Th e HeatNet control can also be 
confi gured for outdoor reset operation, but IAR provides response based on system behavior rather than 
just looking at outdoor temperature.

The HeatNet platform

HeatNet controls are designed to provide an integrated boiler management system on every boiler. Th e 
platform provides multiple levels of selectivity. HeatNet electronics can be operated as a simple single-
boiler control, while still providing intelligent regulation of boiler fi ring rate to match system demand.  
With a few key strokes on the key pad, the HeatNet control can operate as a sophisticated multiple-boiler 
controller, using simple RJ45 cable interfacing between units. Th

  e control can even accept external control 

commands from building managements systems (Modbus standard, with optional bridge for BACnet or 
LonWorks) or 20-milliamp analog input from an external controller.

Th

  e control method used by the HeatNet control is based on digital communications, which eliminates the 

need for analog control signals. Analog signal inputs are supported, but a higher level of control precision, 
repeatability and feedback is gained with digital communications.

Th e HeatNet control can be versatile, providing for operation in multiple ways:

Operation as a stand-alone boiler.
Operation as a boiler in a boiler network, using the on-board HeatNet protocol.
Operation as a member boiler in a boiler management system.
Operation as a member of a remotely-controlled boiler network (20-milliamp regulation).
Setpoint can be determined by the HeatNet control or by a 20-milliamp input signal.

PID response

Th e HeatNet control uses proportional-integral-derivative calculations to determine the response to 
boiler water temperature changes. Th is means it not only looks at how far away the water temperature is 
from the setpoint temperature, but how fast the temperature is changing and how it has responded over 
time. Th is ensures the boiler won’t make sudden unnecessary changes in fi ring rate.

Multiple boiler operation

Th

  e HeatNet control easily interfaces with other HeatNet controls. Multiple boiler operation using HeatNet 

protocol only requires RJ45 cables daisy-chained from boiler to boiler and a few key strokes sett ing up 
control behavior. Th e master boiler is automatically selected by connecting a sensor lead to its HEADER 
sensor terminals. Th e HeatNet control recognizes the sensor and confi gures the boiler as the master. 
Other boilers only need to have an address assigned.

Among the advanced design features of the HeatNet control is the MOD-MAX sett ing. Th is limits the 
fi ring rate of all boilers to a pre-set maximum (50% by default). Th

  is means all of the boilers will be run 

at a very effi  cient level until all boilers are on. Only then can fi ring rate increase above this sett ing. Boiler 
rotation can be fi rst-on/fi rst-off , fi rst-on/last-off , or true rotation (the HeatNet control monitors the total 
on time of all boilers, and rotates their usage so the total on time is the same for all).





HeatNet

Control panel

Содержание KN SERIES

Страница 1: ...pply Followtheinstructionmanualprocedurestoductairtotheboilerairintake Iftheboilerhasbeencontaminatedbyoperation with contaminated air follow the instruction manual guidelines to clean repair or repla...

Страница 2: ...l controller ThecontrolmethodusedbytheHeatNetcontrolisbasedondigitalcommunications whicheliminatesthe needforanalogcontrolsignals Analogsignalinputsaresupported butahigherlevelofcontrolprecision repea...

Страница 3: ...ter cutoff if desired To flow switch when used Used to activate combustion air damper if desired To combustion air damper proving switch required when controlling combustion air damper Indoor air rese...

Страница 4: ...4 P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL The KN boiler with HeatNetTM control...

Страница 5: ...e RS485 interface board and cable above Boiler setup is essentially the same as for method 1 with the exception that each boiler must be assigned both a HeatNet network address and an address for the...

Страница 6: ...service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 10 1 1 2 3 Figure 1 Electrical connection board see item 10 page 3 for location Also see the wiring sum...

Страница 7: ...at pocket ing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See the Boiler manual f...

Страница 8: ...board If there is more than one transformer provide one wire from each transformer common side to one of the IAR negative terminals IAR Sensor wiring Header sensor is required A header sensor must be...

Страница 9: ...P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL Figure 7 KN wiring summary wiring to electrical connection board Method 1 HeatNet modulation local control cont 1 Also see Figure 2 page...

Страница 10: ...erm KN USER S CONTROL MANUAL KN 2 only Figure 8 KN wiring summary wiring to electrical connection board continued see Figure 7 page 9 for terminal strip locations Also see Figure 5 page 7 Method 1 Hea...

Страница 11: ...temperature if member boilers were to input heat to the system without control from the master DHW operation in particular would raise the supply temperature from overriding boilers to the DHW Setpoi...

Страница 12: ...he parameter explanations in Table 8 page 25 through page 29 When adjusting the limit band operating limit OP LIMIT local setpoint LOC SETPOINT and DHW setpoint make sure the operating temperature ban...

Страница 13: ...15 F If the display shows a blank space such as 123_56789ABC the control does not detectthemissingboiler boiler4 ChecktheyellowLEDonthecommunication port of the missing boiler NORMAL connection LED s...

Страница 14: ...lve 31 Present Boiler Detected Overview This method uses an RS485 digital communications cable withtheModbusprotocoltocontrolaboilerorHeatNetnet work TheboilerorboilernetworkwilloperateasintheHeatNetl...

Страница 15: ...has been running For instance Register 29 65536 Register 30 Boiler 1 runtime in seconds Boiler 1 is the master boiler Boilers 2 16 are member boilers 0 4294967295 seconds BACnet or LonWorks protocols...

Страница 16: ...ig ure 12 Install a fused service switch mounted and installed in accordance with all appli cable codes 1 2 3 4 5 6 7 8 9 1 1 2 3 Figure 11 Electrical connection board see item 10 page 3 for location...

Страница 17: ...pocketing in the top of the heat exchanger Thepostpurgecirculatorisfactory pipedandpre wired Do not change the usage the wiring the location or the piping Boiler circulator See the Boiler manual for c...

Страница 18: ...return water temperature sensor DHW wiring ONLY if using DHW override mode The boiler or boilers must be piped with isolation valves and wired for override operation Override of the 4 20mA input will...

Страница 19: ...19 P N 42 9452 8 08 Copyright Hydrotherm KN USER S CONTROL MANUAL Method 3 External 4 20ma control continued 3 Figure 16 KN wiring summary wiring to electrical connection board...

Страница 20: ...yright Hydrotherm KN USER S CONTROL MANUAL Method 3 External 4 20ma control continued 3 KN 2 only Figure 17 KN wiring summary wiring to electrical connection board continued see Figure 7 page 9 for te...

Страница 21: ...revent the boiler for attempting to cycle during the setup process See Control menus and adjustments beginning on page 22 for a complete list of control parameters and explanations Carefully read the...

Страница 22: ...wn providing information on various setpoints and parameters The display LOC SET means the setpoint temperature Figure 18 shows the fac tory default values Accessing setup menus With the display in ST...

Страница 23: ...ARVALUES Display only not changeable here shows values for 8 zones 70 70 70 70 70 70 70 70 OUTDOOR AIR OA SHUTDOWN OFF ON or OFF OA SHUTDOWN OFF OA SETPT 68 F 40 to 100 F OA SETPT 68 F OA RESET OFF ON...

Страница 24: ...minutes 10 MINUTES 0 SECONDS SHED BOILER DLY 2 minutes 0 to 15 minutes 2 MINUTES 0 SECONDS MOD DELAYTIME 10 seconds 0 to 60 minutes 0 MINUTES 10 SECONDS MOD MAX LAST 50 25 to 100 STOP MOD MAX 50 STOP...

Страница 25: ...HW Demand terminals see a closed contact DHW tank temperature control calls for heat for example OP LIMIT SETPOINTS This is the temperature at the boiler outlet or header sensor that will cause the co...

Страница 26: ...e High water at low outside air means the design water temperature for maximum load at ODT or outside design temperature for the installation The other end of the reset curve is the low water temperat...

Страница 27: ...PROTECTION AUX FUNCTIONS Select YES to have the control alarm and disable the DHW demand input if a DHW demand lasts for more than 60 minutes SYSTEM CLOCK Set the system clock time day of week month...

Страница 28: ...left at factory default D ERIVAT ADVANCED SETUP MODULATION PID This parameter should generally be left at factory default BAND ADVANCED SETUP MODULATION PID This parameter should generally be left at...

Страница 29: ...omputer The program will start and show an option screen Select Install USB Drivers to install the program onto the computer After the USB driver installation is complete select Install Firmware Updat...

Страница 30: ...ough the log entries entry number and date are on the first line of the log screen Each log entry includes three screens as described below The top line remains the same in all three and contains the...

Страница 31: ...ected to it If all grounding is correct there may be an issue with radiated or induced electrical noise interference Thismaybecausedbyarcingacrossacontactor scontactswhenstartingapumpmotororalargeelec...

Страница 32: ...up the header sensor is auto detected If the temperature of the header sensor at power up is greater than 25 F and less than 240 F it is considered a valid sensor The boiler will default to the MEMBER...

Отзывы: