7
Operation and maintenance manual, Discfilter HSF2200-1/2F PFC
2.4 Personnel requirements
In order to avoid personal injury and damage to the
equipment, service and maintenance may only be car-
ried out by personnel that have been trained to use the
equipment and are conversant in local regulations. Ser-
vice and maintenance personnel may only handle tho-
se parts of the equipment they have been trained for.
The operator may need to work inside the safety barrier
and in the safety zone during maintenance and set-up
before operation.
2.5 Emergency stop
The filter is equipped with a main power switch (see Fi-
gure 2.3).
To perform an emergency stop, turn the main power
switch to the OFF (0) position.
In the event of a power failure, turn the main power
switch to the OFF (0) position to prevent the filter drum from unintentionally starting to rotate
when the power is reconnected.
2.6 Electrical safety
Electrical installation must be carried out by a qualified electrician and in accordance with local
regulations. Also see Appendix D.
The filter tank or the frame must be connected to ground. Also see section 4.4.
The main power switch/emergency stop must be fitted in accordance with applicable regula-
tions.
2.7 Safety instructions
The filter is activated by turning the main power switch to the ON (1) position and then selecting
HAND or AUTO with the mode selector on the front of the control cabinet. The filter stops if the
mode selector is turned to the 0 (OFF) position.
NB See instructions in section 5.1.
Turn the main power switch to the OFF (0) position and lock it with a padlock before perfor-
ming any work on the filter.
Figure 2.3
A. Pump OFF (0) position
B. Pump ON (1) position
C. Pump switch
D. Mode (0) position
E. Mode (AUTO) position
F. Mode (HAND) position
G. Mode selection switch
H. Main power switch (ON (1) / OFF(0))