52 Hydro-View User Guide HD0531 Rev 2.0.0
Arm Length
and Type
Automatically
Detected
Figure 35: Hydro-Probe Orbiter Arm Selection
If the arm type is not selectable the connected arm is automatically detected by the Hydro-
Probe Orbiter Head Unit (Figure 35).
During the AutoCal procedure, the ceramic face must be clean, dry and free from
obstruction. Once the ‘AutoCal’ button is pressed, the AutoCal measurement will start and
should take approximately 30 seconds (Figure 36). The sensor will then be ready for use
in the mixer.
Figure 36: AutoCal in Progress
Water
Starts a Water calibration measurement. Ensure that the sensors measurement face is
immersed in water (ideally with 0.5% salt by weight) and is free from other obstructions.
Touch the Water button. The sensor then takes a number of readings to establish an
accurate reference point in water.
Air
Starts an Air calibration measurement. Ensure that the sensors measurement face is in air,
is clean, dry and free from other obstructions. Touch the Air button. The sensor then takes
a number of readings to establish an accurate reference point in air.
6.6.2
Temperature Compensation Screen
These settings should not be changed unless advised to do so by a Hydronix
trained engineer.
Figure 37: Temperature Compensation Screen
Содержание HV04
Страница 4: ...4 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 6: ...6 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 12: ...12 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 14: ...14 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 22: ...Mechanical Installation Chapter 2 22 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 28: ...Electrical Installation Chapter 3 28 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 78: ...Material Calibration Chapter 6 78 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 80: ...Default PIN Codes Appendix A 80 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 82: ...USB Memory Stick file format Appendix B 82 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 84: ...Quick Start Rules Appendix C 84 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 86: ...Frequently Asked Questions Appendix D 86 Hydro View User Guide HD0531 Rev 2 0 0 ...
Страница 92: ...Document Cross Reference Appendix G 92 Hydro View User Guide HD0531 Rev 2 0 0 ...