HOW THE OUTDOOR SENSOR WORKS

Outdoor Temperature Reset
The outdoor reset feature monitors outdoor temperature to continuously adjust the boiler 

water to the minimum temperature required to satisfy the heat demand. The feature is 

activated automatically when the Hydrolevel OS-100 or OS-200 is wired to the OR and C 

spade connects on the HydroStat. When connected, Outdoor Reset overrides the Thermal 

Targeting temperature reset method which is built into the HydroStat. The display will toggle 

between boiler temperature (8 seconds) and outdoor temperature (2 seconds). If the sensor 

becomes damaged or disconnected, the control will automatically revert back to the Thermal 

Targeting reset method. The display will no longer toggle outdoor temperature.

Reset Ratio
The HydroStat control’s Outdoor Reset feature uses a reset ratio method to control 

the boiler temperature. The reset ratio determines how much the boiler temperature is 

adjusted for changes in outdoor temperature. A reset ratio of 2.0 means that for each 1 

degree increase in outdoor temperature, the boiler temperature will decrease 2 degrees. 

Conversely, for each 1 degree drop in outdoor temperature, the boiler temperature will 

increase 2 degrees. The control adds 10 degrees to the calculated reset temperature 

and provides a 20 degree differential for burner operation. So, if the control calculates a 

reset temperature of 150°F, it will set a target temperature of 160°F. It will then allow  the 

burner to fire up to 160°F and draw down to 140°F before re-firing. This operation will 

maintain the desired  average temperature of 150°F. You can check the  current target 

temperature at any time, by pressing the Test/Settings button in 4 short intervals. 

Thermal Boost
To insure that the heating system always satisfies a call for heat, the HydroStat control 

is equipped with a thermal boost feature. If the thermostat is not satisfied thirty minutes 

after the boiler reaches the reset temperature, the control will boost the reset temperature 

by 10 degrees. It will continue to boost at 30 minute intervals until the call is satisfied. 

Once the call is satisfied, the control reverts to normal operation, utilizing the calculated 

reset temperature.

Содержание OS-200

Страница 1: ...s completely before proceeding CAUTION To prevent serious burns boiler should be thoroughly cooled before installing or servicing control WARNING Frozen pipes water damage Central heating systems are prone to shut down as a result of power or fuel outages safety related fault conditions or equipment failure Installation of freeze protection monitoring or other precautions is recommended for unatte...

Страница 2: ...uillage et 2 l utilisateur de l appareil doit accepter tout brouillage radioélectrique subi même si le brouillage est susceptible d en compromettre le fonctionnement Warning FCC and IC Radiation Exposure Statement This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment The antenna s used for this equipment must be installed to provide a separation dista...

Страница 3: ...t appliances or other sources of electrical interference Easy access for wiring Approximately 5 feet 1 5 m off the finished floor Grasp the front cover by the fingertip grips on the top and bottom of the enclosure and pull the front cover off The enclosure is either mounted flush onto a wall or it can be placed onto a 2 x 4 non conductive electrical box The mounting holes in the enclosure accept 6...

Страница 4: ...dd a transformer supplied by others as shown below The receiver unit must be powered with 24 VAC Batteries in the Transmitter unit Remove the cover from the transmitter unit Insert the included batteries as marked on the battery holder 1 5V lithium batteries are required to provide the specified battery life and temperature range Alkaline batteries have short life spans and may fail during cold we...

Страница 5: ...evert to a power up condition a temperature of 75 F 24 C will be reported until the first transmission is received up to 10 minutes Communication Power Low Battery Link Wireless Outdoor Sensor 087 Receiver Communication Power Low Battery Link Wireless Outdoor Sensor 087 Receiver STEP 4 INSTALL TRANSMITTER The transmitter should be mounted on a northern exterior wall away from direct sunlight In or...

Страница 6: ...tdoor Reset AND Warm Weather Shutdown Attach the spade connectors to the right and center spade posts OR and C for full outdoor reset functionality including warm weather shutdown protection Wiring this way overrides the Thermal Targeting function of the HydroStat control Warm Weather Shutdown Only WWSD Connect the wire ends to the left and center spade connectors WWSD and C to add warm weather sh...

Страница 7: ...O O R D E S I G N T E M P E R A T U R E B O I L E R T E M P E R A T U R E STEP 6 SETTING THE HYDROSTAT CONTROL continued To set the desired warm weather shutdown temperature Press and hold the TEST SETTING BUTTON and simultaneously adjust the ECONOMY dial to the desired setting To turn the feature off which will allow space heating regardless of outdoor temperature press and hold the TEST SETTING ...

Страница 8: ...ns that for each 1 degree increase in outdoor temperature the boiler temperature will decrease 2 degrees Conversely for each 1 degree drop in outdoor temperature the boiler temperature will increase 2 degrees The control adds 10 degrees to the calculated reset temperature and provides a 20 degree differential for burner operation So if the control calculates a reset temperature of 150 F it will se...

Страница 9: ...hat the communication LED turns green The battery life of the transmitter batteries may have expired This is likely the issue if the batteries have been in extended service They can be replaced with 1 5V lithium batteries The link may have been interrupted Try re linking the devices as described on page 4 3 If the communication LED remains off for over 30 minutes please call Tech Support at 203 77...

Страница 10: ...30307 13 F 25 C 97007 4 F 20 C 72910 5 F 15 C 55303 14 F 10 C 42316 23 F 5 C 32651 32 F 0 C 25395 41 F 5 C 19903 50 F 10 C 15714 59 F 15 C 12493 68 F 20 C 10000 77 F 25 C 8056 86 F 30 C 6530 95 F 35 C 5325 104 F 40 C 4367 113 F 45 C 3601 122 F 50 C 2985 131 F 55 C 2487 140 F 60 C 10K Type 2 NTC Thermistor ...

Страница 11: ... 7 8 W x 7 8 D 120 x 74 x 23 mm Enclosure Transmitter White ABS plastic NEMA 4X Receiver White PVC plastic NEMA Type 1 Packaged Weight 0 92 lb 420g Sensor 10K Type 2 Approvals FCC and IC Operating range Transmitter 40 to 140 F 40 to 60 C Receiver Indoor use only 32 to 122 F 0 to 50 C RH 90 non condensing Receiver power 24 V ac 10 1 VA ...

Страница 12: ...products which is made within such period we will at our option repair or replace such products or refund the purchase price paid to us by you for such products In no event shall Hydrolevel Company be liable for any other loss or damage whether direct indirect incidental or consequential This warranty is your EXCLUSIVE remedy and shall be IN PLACE OF any other warranty or guarantee express or impl...

Отзывы: